买道传感网

分类

商品名称: P+F 倍加福 KFD2-UFT-Ex2.D 本质安全型隔离栅 K-System (DIN rail mounting)

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFD2-UFT-Ex2.D

KFD2-UFT-Ex2.D

产品参数

Display elements LEDs , display
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
IECEx certificate IECEx TUN 04.0007 IECEx TSA 18.0007X
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Rated current I approx. 130 mA
Directive 2014/35/EU EN 61010-1:2010
Power consumption 2.5 W
Programming interface programming socket
Open circuit voltage/short-circuit current_1 18 V / 5 mA
Open loop voltage max. 24 V DC
Influence of ambient temperature_1 0.005 %/K (50 ppm)
Connection side control side
EU-type examination certificate TÜV 99 ATEX 1471
Measuring time frequency measurement: < 100 ms
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output III, IV/input III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Output III, IV/V basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Power P 34 mW (linear characteristic)
Maximum safe voltage U_2 U 40 V DC (Attention! U is no rated voltage.)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Mass 300 g
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Signal type Digital Input
Maximum safe voltage_1 U 253 V (Attention! The rated voltage can be lower.)
Interface/output III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Input I and II terminals 1+, 3-; 4+, 6-: Ex ia
Interface RS 232
Control elements Control panel
Electromagnetic compatibility NE 21:2006
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Response delay ≤ 200 ms
Input I, II/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input III and IV terminals 13+, 14-; 15+, 14- non-intrinsically safe
Maximum safe voltage U 40 V (Attention! U is no rated voltage.)
Labeling space for labeling at the front
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Marking_1 II 3G Ex nA nC IIC T4 Gc
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Output III and IV terminals 19, 20, 21 non-intrinsically safe
Contact loading_1 50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Accuracy_1 < 30 µA
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Voltage U 10.1 V
Input III, IV/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Output III, IV/power supply and collective error basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Power dissipation 2.2 W
Degree of protection IP20
UL approval E223772
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec nC IIC T4 Gc
Load max. 650 Ω
Input EN 60947-5-6:2000
Measuring range 0.001 ... 1000 Hz
Pulse duration min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Maximum safe voltage U_1 U 40 V DC (Attention! U is no rated voltage.)
Control drawing 16-538FM-12
Current range 0 ... 20 mA or 4 ... 20 mA
Collective error message Power Rail
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Current I 13.5 mA
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Configuration via operating buttons via PACTware
Height 119 mm
Width 40 mm
Depth 115 mm
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Output V/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Rated voltage U 20 ... 30 V DC
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Certificate TÜV 02 ATEX 1885 X
Influence of ambient temperature 0.003 %/K (30 ppm)
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Mechanical life 5 x 10 switching cycles
Signal level 1-signal: (external voltage) - 2.5 V max. for 10 mA or 3 V max. for 100 mA (100 mA, short-circuit proof) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: switched off (off-state current ≤ 10 µA)
Output V terminals 8+, 7- non-intrinsically safe
Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Maximum safe voltage_2 U 40 V (Attention! U is no rated voltage.)
Connection screw terminals
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Maximum safe voltage U 40 V DC (Attention! U is no rated voltage.)
Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Resolution_1 < 10 µA
Interface/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V

相关资料