产品参数

Load max. 650 Ω
Electromagnetic compatibility NE 21:2007
Voltage 0.1 % of span
Current output max. 20 µA
Safety Integrity Level (SIL) SIL 2
Labeling space for labeling at the front
Width 40 mm
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Configuration via operating buttons via PACTware
Directive 2014/35/EU EN 61010-1:2010
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Programming interface programming socket
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
RTD max. 0.2 % of span
Measurement loop monitoring_1 sensor breakage
Connection screw terminals
Thermocouples max. 10µV deviation of CJC: ±0.8 K
Rated voltage U 20 ... 30 V DC
Display elements LEDs , display
Mass 300 g
Depth 115 mm
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Types of measuring_1 2-, 3-, 5-wire technology
Cold junction compensation external and internal
Power dissipation/power consumption ≤ 2 W / 2.2 W
Output I, II relay
Output III Analog current output
Connection side control side
Measurement loop monitoring sensor breakage, sensor short-circuit
Potentiometer 0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩ
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Input resistance ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Types of measuring 2-, 3-, 4-wire technology
Rated current I approx. 100 mA
Current range 0 ... 20 mA or 4 ... 20 mA
Collective error message Power Rail
Output III/power supply and collective error reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Height 119 mm
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Temperature effect Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span
Sampling rate approx. 700 ms
Signal type Analog input
Degree of protection IP20
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Measuring current approx. 400 µA
Lead resistance max. 50 Ω
Input/Other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Mechanical life 5 x 10 switching cycles
Open loop voltage max. 24 V DC
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V

相关资料