产品参数

Rated voltage U 16.8 ... 31.2 V DC
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mass approx. 70 g
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accuracy max. 0.1 % of full-scale value
Certificate DEMKO 16 ATEX 1750X
Measurement loop monitoring sensor breakage, lead breakage, short circuit
Power dissipation 0.7 W
Operation time MTBF: 353 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F)
Lead resistance ≤ 100 Ω per line
Fault signal downscale or upscale
Measuring time ≤ 300 ms
Ripple ≤ 10 mV
Power consumption 0.8 W
Connection side control side
RTD < 0.1 K/0.05 % of the measured value
Voltage < 0.1 % of the measured value
Signal type Analog input
Input resistance ≥ 1 MΩ
Influence of ambient temperature < 100 ppm/K of full-scale value
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Marking II 3G Ex nA IIC T4 Gc
Programming interface programming socket
IECEx certificate IECEx UL 16.0116X
Measuring current_1 approx. 200 µA
Measurement loop monitoring_1 sensor breakage, lead breakage, short circuit
Height 97 mm
Core cross section 0.5 ... 2.5 mm (20 ... 14 AWG)
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-15:2010
UL approval E106378
PTC type KT, KTY, ST
Types of measuring 2-, 3-, 4-wire connection
Connection screw terminals
Protection against electrical shock EN 61010-1:2010
Dimensions 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1
Width 6.2 mm
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Measuring current approx. 200 µA
Measurement loop monitoring_2 sensor breakage, lead breakage
Types of measuring_2 3-wire connection
Analog voltage output 0/1 ... 5 V , 0/2 ... 10 V , load ≥ 2 kΩ
Types of measuring_1 2-, 3-, 4-wire connection
Cold junction compensation external (Pt100) and internal , manually
Potentiometer < 0.02 % of the measured value
Input/Other circuits safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V test voltage 3 kV, 50 Hz, 1 min
Output/power supply safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V test voltage 3 kV, 50 Hz, 1 min
Analog current output 0/2 ... 10 mA, 0/4 ... 20 mA, load ≤ 600 Ω
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
IECEx marking Ex nA IIC T4 Gc
Configuration via DIP switches via keys via software
Labeling space for labeling at the front
Degree of protection IP20
Depth 107 mm
Lead resistance_1 max. 100 Ω per line
Thermocouples < 0.3 K/0.1 % of the measured value
Lead resistance_2 max. 10 kΩ
Measuring range 0 ... 5 kΩ