买道传感网

分类

商品名称: P+F 倍加福 KFU8-UFC-Ex1.D SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFU8-UFC-Ex1.D

KFU8-UFC-Ex1.D

产品参数

Safety Integrity Level (SIL) SIL 2
Labeling space for labeling at the front
Input I terminals 1+, 3-: Ex ia
Width 40 mm
Mass 300 g
Mechanical life 5 x 10 switching cycles
Power dissipation/power consumption ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
Pulse duration > 50 µs
Load max. 650 Ω
Influence of ambient temperature_1 0.005 %/K (50 ppm)
Input I/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output III/IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Current I 13.5 mA
Power P 34 mW (linear characteristic)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Connection screw terminals
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Input frequency 0.001 ... 5000 Hz
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Output III terminals 19+, 20- non-intrinsically safe
Accuracy 0.1 % of the measurement value , > 0.001 Hz
Response delay ≤ 200 ms
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output III/start-up override basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Input EN 60947-5-6:2000
Output IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
EU-type examination certificate TÜV 99 ATEX 1471
Display elements LEDs , display
Maximum safe voltage U 253 V AC / 125 V DC (Attention! U is no rated voltage.)
IECEx certificate IECEx TUN 04.0007
Signal level 1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof) 0-signal: switched off (off-state current ≤ 10 µA)
Measuring time < 100 ms
Maximum safe voltage U 40 V (Attention! The rated voltage can be lower.)
Start-up override/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Signal type Digital Input
Programming interface programming socket
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Open circuit voltage/short-circuit current 18 V / 5 mA
Configuration via operating buttons via PACTware
Interface RS 232
Electromagnetic compatibility NE 21:2006
Output IV terminals 8+, 7- non-intrinsically safe
Open loop voltage max. 24 V DC
Measuring range 0.001 ... 5000 Hz
Maximum safe voltage U_1 U 40 V (Attention! U is no rated voltage.)
Maximum safe voltage_2 U 40 V DC (Attention! U is no rated voltage.)
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Rated voltage U 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-11:2012
Connection side control side
Height 119 mm
Depth 115 mm
Maximum safe voltage_1 U 253 V (Attention! The rated voltage can be lower.)
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Directive 2014/35/EU EN 61010-1:2010
Input II terminals 13+, 14- non-intrinsically safe
Current range 0 ... 20 mA or 4 ... 20 mA
Accuracy_1 < 20 µA
Interface/output III basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Control elements Control panel
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Contact loading_1 40 V DC
Resolution 0.1 % of the measurement value , ≥ 0.001 Hz
Influence of ambient temperature 0.003 %/K (30 ppm)
Output III/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Degree of protection IP20
Control drawing 16-538FM-12
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Fault signal downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Resolution_1 < 10 µA
Voltage U 10.1 V