买道传感网

分类

商品名称: P+F 倍加福 KCD2-RR2-Ex1 SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KCD2-RR2-EX1

KCD2-RR2-EX1

产品参数

Rated voltage U 19 ... 30 V DC
Degree of protection IP20
Control drawing_1 116-0332 (cULus)
Influence of ambient temperature I ≥ 1 mA, R ≥ 100 Ω: 0.01 %/K in the range -20 ... +70 °C (-4 ... 158 °F) I < 1 mA or R < 100 Ω: temperature stability reduces in proportion to I or R
Height 119 mm
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Connection side control side
Current I 39.22 mA
Line fault detection yes , at Pt100
Power consumption 0.35 W (24 V and 1 mA sense current), 0.85 W (30 V and 10 mA sense current)
Lead resistance ≤ 10 % of resistance value
Deviation I ≥ 1 mA: ±0.1 % of R or ± 0.1 Ω (the larger value is applicable) I < 1 mA: accuracy reduces in proportion to I . e. g. I = 0.1 mA: ± 1 % of R or 1 Ω (the larger value is applicable).
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Ripple within the supply tolerance
Available voltage 0 ... 4.2 V
FM certificate FM 19 CA 0039 X , FM 19 US 0067 X
Reverse polarity protection for I < 10 mA or U < 20 V
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate BASEEFA 10 ATEX 0061X
Labeling space for labeling at the front
Accuracy 0.1 %
Configuration via DIP switches
Line fault detection_1 < 30 nA
Rated current I < 28 mA
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Fault signal field voltage < 150 mV or > 4 V, depending on lead disconnected
Width 12.5 mm
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Display elements LED
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
IECEx certificate IECEx BAS 10.0024X IECEx BAS 10.0025X
Protection against electrical shock UL 61010-1:2012
Signal type Analog input
Input/Output safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Electromagnetic compatibility NE 21:2017 EN IEC 61326-3-2:2018
Control elements DIP switch
Transmission range 0 ... 10 mA
Mass approx. 100 g
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Certificate BASEEFA 10 ATEX 0062X
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Systematic capability (SC) SC 3
Settling time ≤ 5 ms
Rise time/fall time ≤ 2 ms (10 ... 90%)
Safety Integrity Level (SIL) SIL 2
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
Control drawing 116-0457 (cFMus)
Connection screw terminals
Maximum safe voltage U 250 V (Attention! The rated voltage can be lower.)
Marking_1 II 3G Ex ec IIC T4 Gc
Maximum safe voltage_1 U 250 V (Attention! The rated voltage can be lower.)
UL approval E106378
Voltage U 9.5 V
Depth 114 mm
Power P 93 mW
Output/power supply functional insulation, rated insulation voltage 50 V AC

相关资料