买道传感网

分类

商品名称: P+F 倍加福 KFD2-VR2-Ex1.50M 本质安全型隔离栅 K-System (DIN rail mounting)

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFD2-VR2-EX1.50M

KFD2-VR2-EX1.50M

产品参数

Voltage U 5.5 V DC
Power P 3.3 mW
Connection screw terminals
Display elements LED
Ambient temperature -40 ... 60 °C (-40 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions
After calibration at 20 °C (68 °F): ± 3 µV up to ± 10 mV/± 0.03 % of the span up to +50 mV/± 0.05 % of the span up to -50 mV
Ripple within the supply tolerance
Influence of ambient temperature ± 1 µV/K (typical ± 0.25 µV/K)
Output resistance max. 3 Ω
Degree of protection IP20
Control drawing 116-0334 (cULus)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Width 20 mm
Depth 115 mm
Marking_1 II 3G Ex ec IIC T4 Gc
Rated current I ≤ 11 mA
Power dissipation/power consumption 0.3 W max.
Rated voltage U 19 ... 30 V DC
Electromagnetic compatibility NE 21:2006
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Connection side control side
Height 119 mm
Fault signal sensor breakage: > +100 mV (upscale), < -100 mV (downscale)
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN 60079-11:2012
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Protection against electrical shock UL 61010-1
Labeling space for labeling at the front
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Certificate BASEEFA 09 ATEX 0219X
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Signal type Analog input
EU-type examination certificate BASEEFA 06 ATEX 0040
Output/power supply functional insulation, rated insulation voltage 50 V AC
Absolute < 0.25 K at 30 V voltage supply
UL approval E106378
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Line fault detection 100 nA
Mass approx. 125 g
IECEx certificate IECEx BAS 06.0011 IECEx BAS 09.0103X
Control elements DIP switch
Configuration via DIP switches
Rise time ≤ 1 ms
Current I 2.4 mA
Maximum safe voltage U 250 V (Attention! The rated voltage can be lower.)
Offset voltage/current ≤ 5 µV / ≤ 5 nA
Cut-off frequency 350 Hz (-3 dB)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Load Accuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kΩ
Input resistance min. 20 MΩ
Transmission range -50 ... 50 mV