买道传感网

分类

商品名称: P+F 倍加福 KFU8-UFT-Ex2.D 本质安全型隔离栅 K-System (DIN rail mounting)

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFU8-UFT-EX2.D

KFU8-UFT-EX2.D

产品参数

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Current range 0 ... 20 mA or 4 ... 20 mA
Load max. 650 Ω
Width 40 mm
Maximum safe voltage U 253 V AC / 125 V DC (Attention! U is no rated voltage.)
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage U_2 U 40 V DC (Attention! U is no rated voltage.)
Maximum safe voltage_2 U 40 V (Attention! U is no rated voltage.)
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Labeling space for labeling at the front
Electromagnetic compatibility NE 21:2006
Signal type Digital Input
Input EN 60947-5-6:2000
Measuring range 0.001 ... 1000 Hz
Voltage U 10.1 V
Configuration via operating buttons via PACTware
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
EU-type examination certificate TÜV 99 ATEX 1471
Pulse duration min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Input I, II/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Maximum safe voltage U 40 V (Attention! U is no rated voltage.)
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Control drawing 16-538FM-12
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output III, IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Display elements LEDs , display
Depth 115 mm
Influence of ambient temperature 0.003 %/K (30 ppm)
Response delay ≤ 200 ms
Accuracy_1 < 30 µA
Input III, IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Power P 34 mW (linear characteristic)
Degree of protection IP20
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-11:2012
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Connection side control side
Power consumption 2.5 W / 5 VA
Output III and IV terminals 19, 20, 21 non-intrinsically safe
Open loop voltage max. 24 V DC
Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Influence of ambient temperature_1 0.005 %/K (50 ppm)
Interface/output III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Rated voltage U 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Power dissipation 2.2 W / 3.5 VA
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Open circuit voltage/short-circuit current_1 18 V / 5 mA
Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: switched off (off-state current ≤ 10 µA)
Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Interface RS 232
Mass 300 g
Height 119 mm
Mechanical life 5 x 10 switching cycles
Maximum safe voltage_1 U 253 V (Attention! The rated voltage can be lower.)
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Contact loading_1 40 V DC
Output V terminals 8+, 7- non-intrinsically safe
Output V/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Current I 13.5 mA
Connection screw terminals
IECEx certificate IECEx TUN 04.0007
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Measuring time frequency measurement: < 100 ms
Resolution_1 < 10 µA
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output III, IV/V basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Input I and II terminals 1+, 3-; 4+, 6-: Ex ia
Input III and IV terminals 13+, 14-; 15+, 14- non-intrinsically safe
Maximum safe voltage U_1 U 40 V (Attention! U is no rated voltage.)
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Control elements Control panel
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Rated current I approx. 130 mA
Directive 2014/35/EU EN 61010-1:2010
Programming interface programming socket
Accuracy_2 0.1 %
Output III, IV/input III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V

相关资料