产品参数
| Switching frequency | ≤ 5 kHz |
| Marking_1 | II 3G Ex ec IIC T4 Gc |
| Configuration | via DIP switches |
| Width | 12.5 mm |
| EU-type examination certificate | BASEEFA 13 ATEX 0080 |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Signal type | Digital Input |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
| Depth | 114 mm |
| Power | P 45 mW (linear characteristic) |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Response time | ≤ 200 µs |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
| Connection | screw terminals |
| Ripple | ≤ 10 % |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Pulse/Pause ratio | min. 100 µs / min. 100 µs |
| Output I | signal ; Transistor |
| Protection against electrical shock | IEC 61010-1:2010 |
| Mass | approx. 100 g |
| Voltage | U 10.5 V |
| Control drawing | 116-0374 (cULus) |
| Connection side | control side |
| Output/Output | not available , common pole terminal 9+ |
| Display elements | LEDs |
| Labeling | space for labeling at the front |
| IECEx certificate | IECEx BAS 13.0046 IECEx CML 19.0147X |
| Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
| Safety Integrity Level (SIL) | SIL 2 |
| Electromagnetic compatibility | NE 21:2011 |
| Maximum safe voltage | U 253 V AC (Attention! U is no rated voltage.) |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Output II | signal or fault message ; Transistor |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
| Current | I 17.1 mA |
| Certificate | CML 19 ATEX 4410 X |
| Signal level | 1-signal: (supply voltage) - 3 V max. for 50 mA 0-signal: blocked output (off-state current ≤ 10 µA) |
| Control elements | DIP switch |
| Rated current | I 50 mA |
| Collective error message | Power Rail |
| Input | Ex ia |
| Systematic capability (SC) | SC 3 |
| Degree of protection | IP20 |
| Power dissipation | ≤ 700 mW including maximum power dissipation in the output |
| Height | 119 mm |
| Maximum safe voltage_1 | U 253 V AC (Attention! The rated voltage can be lower.) |
| Output/power supply | not available , common pole terminal 9+ |
| Rated voltage | U 30 V DC |
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |