买道传感网

分类

商品名称: P+F 倍加福 HiC2841 SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: HIC2841

HIC2841

产品参数

Mounting on termination board
EU-type examination certificate BVS 09 ATEX E 157
Power dissipation ≤ 500 mW
Configuration via DIP switches
Coding pin 1 and 2 trimmed For further information see system description.
Signal type Digital Input
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Maximum safe voltage_1 U 253 V AC (Attention! The rated voltage can be lower.)
Output II signal or fault message ; Transistor
Output/power supply basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
IECEx certificate IECEx BVS 09.0060
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Power P 45 mW (linear characteristic)
Relative humidity ≤ 90 % , non-condensing
Factory setting input close, transistor closed, lead fault detection enabled
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Labeling space for labeling at the front
Control elements DIP switch
Ripple ≤ 10 %
Rated values acc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Pulse/Pause ratio min. 100 µs / min. 100 µs
Rated current I 50 mA
Connection SL1: 6b
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Current I 17.1 mA
Input Ex ia, Ex iaD
Response time ≤ 200 µs
Protection against electrical shock IEC 61140
Connection side control side
Switching frequency ≤ 5 kHz
Maximum safe voltage U 253 V AC (Attention! U is no rated voltage.)
Galvanic isolation EN 50178:1997
Degree of protection IP20
Mass approx. 90 g
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
UL approval E106378
Power consumption ≤ 600 mW
Voltage U 10.5 V
Display elements LEDs
Electromagnetic compatibility NE 21:2012 For further information see system description.
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Signal level 1-signal: (external voltage) - 1 V max. for 50 mA (T = 25 °C (77 °F)) 0-signal: blocked output (off-state current ≤ 10 µA)
Safety Integrity Level (SIL) SIL 2
Rated voltage U 30 V DC
Dimensions 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000
Control drawing 116-0331
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Output/Output basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Output I signal ; Transistor
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Systematic capability (SC) SC 3
Output type open collector transistor (internal fault bus)