产品参数

Connection screw terminals
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Width 12.5 mm
Rated current I ≤ 46 mA
Output I signal ; relay
Functional safety IEC/EN 61508:2010
Degree of protection IP20
Mass approx. 100 g
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Systematic capability (SC) SC 3
Power consumption ≤ 900 mW
Labeling space for labeling at the front
Depth 114 mm
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Power dissipation ≤ 900 mW
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Signal type Digital Input
Display elements LEDs
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Ripple ≤ 10 %
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Height 119 mm
Contact loading 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load
Electromagnetic compatibility NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Input EN 60947-5-6:2000
Pulse/Pause ratio min. 20 ms / min. 20 ms
Safety Integrity Level (SIL) SIL 2
Switching frequency ≤ 10 Hz
Directive 2014/35/EU EN 61010-1:2010+A1:2019+A1:2019/AC:2019
Rated voltage U 19 ... 30 V DC
Connection side control side
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Configuration via DIP switches
Minimum switch current 2 mA / 24 V DC
Mechanical life 10 switching cycles
Rated values acc. to EN 60947-5-6 (NAMUR)
Output II signal ; relay