买道传感网

分类

商品名称: P+F 倍加福 KFD2-CRG2-Ex1.D SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFD2-CRG2-EX1.D

KFD2-CRG2-EX1.D

产品参数

Labeling space for labeling at the front
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Resolution ≤ 10 µA
Maximum safe voltage U U 40 V (Attention! The rated voltage can be lower.)
Input resistance 45 Ω (terminals 2, 3)
Available voltage ≥ 15 V at 20 mA
Equipment terminals 1+, 3-
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Certificate TÜV 02 ATEX 1885 X
Output III terminals 8+, 7- non-intrinsically safe
Maximum safe voltage_1 U 253 V AC / 40 V DC (Attention! U is no rated voltage.)
Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Voltage_3 U 25.8 V
Power_2 P 720 mW
Safety Integrity Level (SIL) SIL 2
Directive 2014/35/EU EN 61010-1:2010
Response delay ≤ 200 ms at bounce from 0 ... 20 mA
Influence of ambient temperature_1 0.005 %/K (50 ppm)
Output III/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Power consumption 2.5 W
Rated current I approx. 130 mA
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Control drawing 16-554FM-12 (cFMus)
Connection screw terminals
Mechanical life 5 x 10 switching cycles
Maximum safe voltage U 40 V DC (Attention! The rated voltage can be lower.)
Marking_1 II 3G Ex nA nC IIC T4
Contact loading_1 50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Control elements Control panel
Interface RS 232
UL approval E223772
Input signal 0/4 ... 20 mA
Current_1 I 115 mA
EU-type examination certificate TÜV 01 ATEX 1701
Power dissipation 2 W
Connection side control side
Display elements LEDs , display
Current I 93 mA
IECEx certificate IECEx TUN 09.0007 IECEx TSA 18.0007X
Line fault detection breakage I < 0.2 mA; short-circuit I > 22 mA
Current range 0 ... 20 mA or 4 ... 20 mA
Input Ex ia
Power P 0.603 W
Reaction time < 650 ms at bounce from 0 ... 20 mA at the input, 90 % of output full-scale value
Equipment_2 terminals 1+, 2 / 3-
Open circuit voltage/short-circuit current 24 V / 33 mA
Height 119 mm
Depth 115 mm
Output signal 0 ... 20 mA or 4 ... 20 mA
Current_2 I 0.3 mA
Rated voltage U 20 ... 30 V DC
Degree of protection IP20
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec nC IIC T4 Gc
Programming interface programming socket
Open loop voltage max. 24 V DC
Interface/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Width 40 mm
Maximum safe voltage_2 U 40 V (Attention! The rated voltage can be lower.) , RS 232
Voltage_1 U < 30 V
Current_3 I 112 mA
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Signal type Analog input
Electromagnetic compatibility NE 21:2006
Accuracy < 30 µA
Accuracy_1 < 20 µA
Voltage_2 U 5 V
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Energized/De-energized delay 0 ... 250 s , adjustable
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Influence of ambient temperature 0.003 %/K (30 ppm)
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Configuration via operating buttons via PACTware
Power_1 P 0.3 mW
Mass 300 g
Voltage U 25.8 V
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Load max. 650 Ω
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Equipment_1 terminals 2-, 3

相关资料