商品名称: P+F 倍加福 KFU8-UFC-1.D.FA 信号调节器 K-System (DIN rail, highly functional)
品牌名称: P+F 倍加福
分类名称: 其他
商品订货号:
商品型号: KFU8-UFC-1.D.FA
产品参数
| Safety Integrity Level (SIL) | SIL 2 |
| Input resistance | 4.7 kΩ |
| Directive 2014/30/EU | EN 61326-1:2006 |
| Directive 2014/35/EU | EN 61010-1:2010 |
| Input I | 2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact |
| Active/Passive | I > 4 mA (for min. 100 ms) / I < 1.5 mA |
| Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Output III/IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V |
| Signal type | Digital Input |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Programming interface | programming socket |
| Switching point/switching hysteresis | logic 1: > 2.5 mA ; logic 0: < 1.9 mA |
| Line fault detection | breakage I ≤ 0.15 mA; short-circuit I > 4 mA |
| Interface/output III | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V |
| Influence of ambient temperature | 0.003 %/K (30 ppm) |
| Open circuit voltage/short-circuit current_1 | 18 V / 5 mA |
| Resolution | 0.1 % of the measurement value , ≥ 0.001 Hz |
| Resolution_1 | < 10 µA |
| Load | max. 650 Ω |
| Degree of protection | IP20 |
| Width | 40 mm |
| Fault signal | downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43) |
| Open loop voltage | max. 24 V DC |
| Output III/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Output IV/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Display elements | LEDs , display |
| Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Output I, II | signal, relay |
| Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Labeling | space for labeling at the front |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Output IV | analog |
| Response delay | ≤ 200 ms |
| Connection side | control side |
| Open circuit voltage/short-circuit current | 22 V / 40 mA |
| Electromagnetic compatibility | NE 21:2006 |
| Mass | 300 g |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
| Depth | 115 mm |
| Input frequency | 0.001 ... 10000 Hz |
| Output III | electronic output, passive |
| Configuration | via operating buttons via PACTware |
| Power dissipation/power consumption | ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA |
| Input II | startup override: 1 ... 1000 s, adjustable in steps of 1 s |
| Start-up override/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Rated voltage | U 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz |
| Accuracy | 0.1 % of the measurement value , > 0.001 Hz |
| Measuring range | 0.001 ... 10000 Hz |
| Pulse duration | > 50 µs |
| Contact loading_1 | 40 V DC |
| Current range | 0 ... 20 mA or 4 ... 20 mA |
| Accuracy_1 | < 20 µA |
| Influence of ambient temperature_1 | 0.005 %/K (50 ppm) |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Connection | screw terminals |
| Height | 119 mm |
| Measuring time | < 100 ms |
| Mechanical life | 5 x 10 switching cycles |
| Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA) |
| Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |