商品名称: P+F 倍加福 KFD2-RSH-1.2D.FL3 信号调节器 K-System (DIN rail, highly functional)

品牌名称: P+F 倍加福

分类名称: 其他

商品订货号:

商品型号: KFD2-RSH-1.2D.FL3

KFD2-RSH-1.2D.FL3

产品参数

Safety Integrity Level (SIL) SIL 3
Connectable voltage 50 ... 230 V AC 60 ... 110 V DC
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility NE 21:2017 , IEC/EN 61326-3-2:2018 , EN 61326-3-1:2017
Width 20 mm
Pulse/Pause ratio min. 150 ms / min. 150 ms with disabled internal fault detection min. 1 s / min. 1 s with enabled internal fault detection
Directive 2006/42/EC EN 62061:2005+AC:2010+A1:2013+A2:2015 , EN/ISO 13849-1:2015
Fuse rating 2.5 A (scope of delivery) max. 5 AT, recommended maximum utilization of the fuse: 80 %
Contact loading 30 V DC/ 0.5 A resistive load
Minimum switch current 10 mA
Rated current I 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card)
Input/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 V
Display elements LEDs
Labeling space for labeling at the front
Directive 2014/35/EU EN 61010-1:2010
Signal level 0-signal: -5 ... 5 V DC 1-signal: 19 ... 26.4 V DC
Performance level (PL) PL e
Inrush current < 200 mA after 100 µs
Connection screw terminals
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating.
Mass approx. 142 g
Reaction time < 2 s
Height 119 mm
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Signal type Digital Output
Systematic capability (SC) SC 3
Connection side field side
Depth 115 mm
Mechanical life 10 switching cycles
Power dissipation < 3.3 W at 5 A , see derating curves
Configuration via DIP switches
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Line fault detection low voltage < 35 V AC undercurrent: 10 mA AC; overcurrent: 5.5 A AC (relay energized) breakage: 48 kΩ; short-circuit: 29 Ω (load, relay de-energized)
Input current max. 35 mA at 24 V DC , max. 44 mA at 19 V DC , with enabled internal fault detection
Test pulse length max. 2 ms from DO card
Input/fault indication output basic insulation according to IEC/EN 61010-1, rated insulation voltage 30 V
Rated voltage U 19 ... 26.4 V DC
Power consumption < 1.7 W , includes the power consumption of the digital input , see derating curves
Degree of protection IP20
Switching frequency < 3 Hz with disabled internal fault detection < 0.5 Hz with enabled internal fault detection
Output/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V