买道传感网

分类

商品名称: P+F 倍加福 KCD2-SLD-Ex1.1045 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

品牌名称: P+F 倍加福

分类名称: 执行器

商品订货号:

商品型号: KCD2-SLD-Ex1.1045

KCD2-SLD-Ex1.1045

产品参数

Mass approx. 150 g
Electromagnetic compatibility NE 21:2012 , EN 61326-3-2:2008 For further information see system description.
Systematic capability (SC) SC 3
Output II/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 V
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010
Mechanical life 10 switching cycles
Internal resistor R 285 Ω
Output/other circuits basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Connection_1 terminals 7, 8 , non-intrinsically safe
Safety Integrity Level (SIL) SIL 3
Current I 93 mA
Configuration via DIP switches
Output I Ex ia
Degree of protection IP20
Signal type Digital Output
Power dissipation 1.4 W at 24 V, 220 Ω load
Connection side field side
Connection screw terminals
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Maximum safe voltage_1 U 60 V (Attention! The rated voltage can be lower.)
Test current max. 350 µA , calculated by I = 4.7 V / (15 kΩ + R )
Rated voltage U 19 ... 30 V DC loop powered
IECEx marking Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
Signal level loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited to 5 mA) 0-signal: 0 ... 5 V DC
Power P 605 mW
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Control drawing 116-0448 (cULus)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
IECEx certificate IECEx EXA 17.0001X
Maximum safe voltage_2 U 60 V (Attention! The rated voltage can be lower.)
Input current 75 mA at 24 V, 220 Ω load
Labeling space for labeling at the front
Maximum safe voltage U 60 V (Attention! The rated voltage can be lower.)
Open loop voltage U typ. 24.6 V
Load nominal 0.05 ... 18 kΩ , valid range for line fault detection (LFD)
Output II fault signal
Current limit I 45 mA
Output I/other circuits safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V
Rated current I 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card)
Contact loading 30 V DC/ 0.5 A resistive load
Display elements LEDs
Protection against electrical shock EN 61010-1:2010
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating.
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Control elements DIP switch
EU-type examination certificate EXA 17 ATEX 0002 X
Marking II 3(1)G Ex nC ec [ia Ga] IIC T4 Gc [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Voltage U 26 V
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
UL approval E106378
Test pulse length max. 2 ms from DO card
Inrush current < 200 mA , 10 ms loop powered