产品参数

Mass approx. 100 g
Dimensions 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate CESI 06 ATEX 021 X
Voltage U 25.2 V
Electromagnetic compatibility NE 21:2017 EN 61326-3-2:2018
Current I 100 mA
Load 0 ... 650 Ω
Output/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Safety Integrity Level (SIL) SIL 2
Connection screw terminals
Input voltage open loop voltage of the control system < 30 V
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Rated voltage U 19 ... 30 V DC
Certificate CESI 19 ATEX 021 X
Power P 630 mW
Display elements LED
Input signal 4 ... 20 mA , limited to approx. 26 mA
Control drawing_1 116-0459 (cULus)
IECEx certificate IECEx CES 06.0001X
Influence of ambient temperature < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
UL approval E106378
Ripple 20 mV
Input/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Deviation at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis
Frequency range field side into the control side: bandwidth with 0.5 V signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 V signal 0 ... 3 kHz (-3 dB)
Output Ex ia
Maximum safe voltage U 250 V AC (Attention! U is no rated voltage.)
Systematic capability (SC) SC 3
Protection against electrical shock UL 61010-1:2019
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Labeling space for labeling at the front
Marking_1 II 3G Ex ec IIC T4 Gc
Height 124 mm
Voltage drop approx. 6 V at 20 mA
Rated current I ≤ 30 mA at 24 V
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018
Connection side field side
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Width 12.5 mm
Power consumption ≤ 700 mW
Equipment terminals 1+, 2-
Internal inductance L negligible
FM certificate FM 18 CA 0116 X , FM 19 US 0117 X
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Rise time 10 to 90 % ≤ 10 ms
Input resistance > 100 kΩ, with field wiring open
Internal capacitance C 5.7 nF
Degree of protection IP20
Control drawing 116-0469 (cFMus)
Signal type Analog output
Power dissipation ≤ 600 mW at 20 mA and 500 Ω load
Depth 114 mm