买道传感网

分类

商品名称: P+F 倍加福 KCD2-STC-Ex1.2O SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KCD2-STC-Ex1.2O

KCD2-STC-Ex1.2O

产品参数

Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
Marking_1 II 3G Ex nA IIC T4 Gc
Width 12.5 mm
Power P 656 mW
Ripple max. 50 µA
Protection against electrical shock UL 61010-1:2012
Voltage_2 U 30 V
Electromagnetic compatibility NE 21:2012 EN 61326-3-2:2008
Load channel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V) channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
Control elements DIP switch
Maximum safe voltage_1 U 250 V (Attention! The rated voltage can be lower.)
Systematic capability (SC) SC 3
Rise time/fall time 2 ms
Equipment_1 terminals 3+, 4-
Internal capacitance C 10 nF
IECEx certificate IECEx BAS 13.0043X
Mass approx. 100 g
EU-type examination certificate BASEEFA 13 ATEX 0077 X
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Certificate BASEEFA 13 ATEX 0078 X
Configuration via DIP switches
Depth 114 mm
Voltage drop terminals 3, 4: ≤ 6.1 V at 20 mA
Power dissipation approx. 1.4 W at 20 mA transfer current, 250 Ω in both outputs
Maximum safe voltage U 250 V (Attention! The rated voltage can be lower.)
Height 124 mm
Power consumption 2 W
Input signal 0/4 ... 20 mA
Output signal 0/4 ... 20 mA or 0/1 ... 5 V
Note Both output loads must be connected to ensure complete and correct operation within the technical specification.
Rated voltage U 19 ... 30 V DC
Display elements LED
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Current I 93 mA
Available voltage terminals 1+, 2-: ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA
Deviation I < 20 µA (0.1 %); V < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V
Power_2 P 1.6 mW
Short-circuit current terminals 1+, 2-: 25 mA
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Control drawing 116-0380 (cULus)
Influence of ambient temperature current output: 0.25 µA/K voltage output: 80 µV/K
Settling time 6 ms
Equipment terminals 1+, 2-
Internal inductance L 0 mH
Signal type Analog input
Connection screw terminals
Output/power supply functional insulation, rated insulation voltage 50 V AC
Voltage_1 U 28.2 V
Power_1 P 700 mW
Safety Integrity Level (SIL) SIL 2
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions
Dimensions 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Connection side control side
Output/Output functional insulation, rated insulation voltage 50 V AC
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Frequency range field side into the control side: bandwidth with 0.5 V signal 0 ... 6 kHz (-3 dB) control side into the field side: bandwidth with 0.5 V signal 0.3 ... 6 kHz (-3 dB)
Degree of protection IP20
Voltage U 25.2 V
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Labeling space for labeling at the front
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Input resistance terminals 1+, 2-: max. 500 Ω (BRAIN) (250 Ω load)
Current_1 I 115 mA
Voltage_3 U 5 V
Current_2 I 6.8 mA