买道传感网

分类

商品名称: P+F 倍加福 HiD2872 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: HiD2872

HiD2872

产品参数

Display elements LEDs
Signal level 1-signal: 15...30 V DC (current limited to 3 mA) or contact close (internal 10 kΩ pull-up) 0-signal: 0...5 V DC or contact open
Open loop voltage U approx. 22.5 V
EU-type examination certificate CESI 10 ATEX 036
Energized/De-energized delay - bus powered: filter OFF: 1 ms, filter ON: 10 ms - loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load)
Internal resistor R approx. 240 Ω
Fault current 4 mA pulsing (20 ms ON, 200 ms OFF)
Mass approx. 140 g
Dimensions 18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Voltage U 26 V
Output Ex ia Ga, Ex ia Da, Ex ia Ma
IECEx certificate IECEx CES 10.0013
Depth 130 mm
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mounting on termination board
Switching frequency f - bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz - loop powered: max. 10 Hz
Certificate PF 10 CERT 1729 X
Current limit I 55 mA
Rated voltage U 20.4 ... 30 V DC loop powered 20.4 ... 30 V DC bus powered via Termination Board
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Input current 62 mA at 24 V, 300 Ω load (per channel)
Current I 110 mA
Output type open collector transistor (internal fault bus)
Coding pin 1 and 4 trimmed For further information see system description.
Safety Integrity Level (SIL) SIL 3
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Control drawing 366-005CS-12B (cCSAus)
Labeling space for labeling at the front
Height 114 mm
Connection side field side
Connection SL1: 6b
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Marking_1 II 3G Ex nA IIC T4 Gc
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Power P 715 mW
Output/Output safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
Electromagnetic compatibility NE 21:2006 For further information see system description.
Configuration via DIP switches
Width 18 mm
Control input external switch (dry contact or open collector) non isolated or logic signal input fully floating
Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Signal type Digital Output
Power dissipation 1 W at 24 V, 300 Ω load (per channel) for loop powered
Maximum safe voltage U 253 V AC (Attention! U is no rated voltage.)
Control elements DIP switch
Inrush current 0.2 A , 15 ms loop powered
Fault level lead short-circuit detection at < 25 Ω lead breakage detection at > 100 kΩ typical
Output/power supply, inputs, and collective error safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Degree of protection IP20
Load nominal 0.1 ... 5 kΩ