商品名称: P+F 倍加福 HiD2872 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3
品牌名称: P+F 倍加福
分类名称: 安全传感器
商品订货号:
商品型号: HiD2872

产品参数
| Display elements | LEDs |
| Signal level | 1-signal: 15...30 V DC (current limited to 3 mA) or contact close (internal 10 kΩ pull-up) 0-signal: 0...5 V DC or contact open |
| Open loop voltage | U approx. 22.5 V |
| EU-type examination certificate | CESI 10 ATEX 036 |
| Energized/De-energized delay | - bus powered: filter OFF: 1 ms, filter ON: 10 ms - loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load) |
| Internal resistor | R approx. 240 Ω |
| Fault current | 4 mA pulsing (20 ms ON, 200 ms OFF) |
| Mass | approx. 140 g |
| Dimensions | 18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D) |
| Voltage | U 26 V |
| Output | Ex ia Ga, Ex ia Da, Ex ia Ma |
| IECEx certificate | IECEx CES 10.0013 |
| Depth | 130 mm |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Mounting | on termination board |
| Switching frequency | f - bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz - loop powered: max. 10 Hz |
| Certificate | PF 10 CERT 1729 X |
| Current limit | I 55 mA |
| Rated voltage | U 20.4 ... 30 V DC loop powered 20.4 ... 30 V DC bus powered via Termination Board |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| Input current | 62 mA at 24 V, 300 Ω load (per channel) |
| Current | I 110 mA |
| Output type | open collector transistor (internal fault bus) |
| Coding | pin 1 and 4 trimmed For further information see system description. |
| Safety Integrity Level (SIL) | SIL 3 |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Control drawing | 366-005CS-12B (cCSAus) |
| Labeling | space for labeling at the front |
| Height | 114 mm |
| Connection side | field side |
| Connection | SL1: 6b |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Marking_1 | II 3G Ex nA IIC T4 Gc |
| IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Power | P 715 mW |
| Output/Output | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V |
| Electromagnetic compatibility | NE 21:2006 For further information see system description. |
| Configuration | via DIP switches |
| Width | 18 mm |
| Control input | external switch (dry contact or open collector) non isolated or logic signal input fully floating |
| Relative humidity | 5 ... 90 %, non-condensing up to 35 °C (95 °F) |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Signal type | Digital Output |
| Power dissipation | 1 W at 24 V, 300 Ω load (per channel) for loop powered |
| Maximum safe voltage | U 253 V AC (Attention! U is no rated voltage.) |
| Control elements | DIP switch |
| Inrush current | 0.2 A , 15 ms loop powered |
| Fault level | lead short-circuit detection at < 25 Ω lead breakage detection at > 100 kΩ typical |
| Output/power supply, inputs, and collective error | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
| Degree of protection | IP20 |
| Load | nominal 0.1 ... 5 kΩ |