产品参数

Connection 3+, 6+, 2-, 5-, 1 shield, 4 shield
Core cross section up to 2.5 mm
Rated voltage_1 24 ... 26 V
Power dissipation max 2.5 W
Connection_1 terminals 7 RxD/TxD-P, 8 RxD/TxD-N, 9 shield, 10 FE
Baud rate 1.5 MBit/s max.
Housing material Polycarbonate
CSA approval CSA 16.70064204
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mounting DIN rail mounting
PROFIBUS DP/PROFIBUS PA functional insulation acc. to IEC 62103, rated insulation voltage 50 V AC /70 V DC
Number of segments 1
Shock resistance 15 g 11 ms
Marking II 3G Ex ec IIC T4 Gc
PROFIBUS DP PROFIBUS with RS-485 transmission technology
Switch PROFIBUS DP terminator
LED PA red 2 Hz flashing: No PA communication or overload Off: PA communication OK
Installation in hazardous area Zone 2 / Div. 2
LED DP/ERR red 2 Hz flashing: DP error red on: Hardware error red off: DP communication detected
Electromagnetic compatibility NAMUR NE 21
Relative humidity < 95 % non-condensing
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
LED PWR green: Power on
PROFIBUS DP/Supply basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC
Vibration resistance 1 g 10 ... 150 Hz
Pollution degree max. 2, according to IEC 60664
Mass 180 g
Approved for Class I, Division 2, Groups A, B, C, D Class I, Zone 2, Ex nA IIC T4 Gc
Climatic conditions DIN IEC 721
IECEx approval IECEx TUR 16.0006X
Rated current max. 400 mA
Directive 2014/30/EU EN 61326-1:2013
Ambient temperature -40 ... 60 °C (-40 ... 140 °F)
Certificate TÜV 16 ATEX 7831 X
Terminating impedance 100 Ω , integrated
PROFIBUS PA/Supply basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Connection type screw terminal , pluggable
Rated voltage U 12.6 ... 13.4 V
Degree of protection IP20
Fieldbus standard EN 50170/2
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018
Approved for_1 Ex ec IIC T4 Gc
Ripple ≤ 10 %