买道传感网

分类

商品名称: P+F 倍加福 KCD2-SR-Ex2.SP SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KCD2-SR-Ex2.SP

KCD2-SR-Ex2.SP

产品参数

Rated current I ≤ 46 mA
Signal type Digital Input
Power dissipation ≤ 900 mW
Labeling space for labeling at the front
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Ripple ≤ 10 %
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
UL approval E106378
Output II signal ; relay
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Display elements LEDs
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Power P 34 mW (linear characteristic)
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
Safety note If load voltage > 50 V, de-energize before removing the terminals.
Contact loading Zone 2 : 50 V AC/2 A/cos φ > 0.75; 30 V DC/2 A resistive load
Directive 2014/35/EU EN 61010-1:2010+A1:2019+A1:2019/AC:2019
Electromagnetic compatibility NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
Configuration via DIP switches
Maximum safe voltage_2 U 40 V DC (Attention! U is no rated voltage.)
Rated values acc. to EN 60947-5-6 (NAMUR)
Functional safety IEC/EN 61508:2010
Degree of protection IP20
Mass approx. 100 g
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Marking II 3(1)G Ex ec nC [ia Ga] IIC T4 Gc , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] I
Power consumption ≤ 900 mW
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
EU-type examination certificate BASEEFA 06 ATEX 0092 X
Voltage U 10.5 V
Connection side control side
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
IECEx certificate IECEx BAS 06.0025 X
Maximum safe voltage_1 U 253 V AC (Attention! The rated voltage can be lower.)
Output I signal ; relay
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Rated voltage U 19 ... 30 V DC
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Current I 13 mA
Maximum safe voltage U 253 V AC (Attention! U is no rated voltage.)
Control elements DIP switch
Safety Integrity Level (SIL) SIL 2
Control drawing 116-0477 (cULus)
Connection spring terminals
Mechanical life 10 switching cycles
Systematic capability (SC) SC 3
Pulse/Pause ratio min. 20 ms / min. 20 ms
Minimum switch current 2 mA / 24 V DC
Switching frequency ≤ 10 Hz
IECEx marking Ex ec nC [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Input Ex ia
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA

相关资料