买道传感网

分类

商品名称: P+F 倍加福 KFU8-GUT-1.D 信号调节器 K-System (DIN rail, highly functional)

品牌名称: P+F 倍加福

分类名称: 模块

商品订货号:

商品型号: KFU8-GUT-1.D

KFU8-GUT-1.D

产品参数

Safety Integrity Level (SIL) SIL 2
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Mass 300 g
Height 119 mm
Input/Other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Degree of protection IP20
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Measuring current approx. 400 µA
Measurement loop monitoring sensor breakage, sensor short-circuit
Measurement loop monitoring_1 sensor breakage
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Labeling space for labeling at the front
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Power dissipation/power consumption ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
Sampling rate approx. 700 ms
Input resistance ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Mechanical life 5 x 10 switching cycles
Directive 2014/35/EU EN 61010-1:2010
Lead resistance max. 50 Ω
Cold junction compensation external and internal
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Temperature effect Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span
Current range 0 ... 20 mA or 4 ... 20 mA
Connection side control side
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
RTD max. 0.2 % of span
Potentiometer 0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩ
Output I, II relay
Open loop voltage max. 24 V DC
Load max. 650 Ω
Display elements LEDs , display
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Voltage 0.1 % of span
Configuration via operating buttons via PACTware
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Electromagnetic compatibility NE 21:2007
Depth 115 mm
Types of measuring 2-, 3-, 4-wire technology
Types of measuring_1 2-, 3-, 5-wire technology
Thermocouples max. 10µV deviation of CJC: ±0.8 K
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Current output max. 20 µA
Output III/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Signal type Analog input
Connection screw terminals
Rated voltage U 20 ... 90 V DC / 48 ... 253 V AC
Width 40 mm
Programming interface programming socket
Output III Analog current output