买道传感网

分类

商品名称: P+F 倍加福 KFD2-GUT-Ex1.D SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFD2-GUT-Ex1.D

KFD2-GUT-Ex1.D

产品参数

Signal type Analog input
Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Mechanical life 5 x 10 switching cycles
Labeling space for labeling at the front
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Current I 8 mA
Power dissipation/power consumption ≤ 2 W / 2.2 W
Programming interface programming socket
Output III Analog current output
Control elements Control panel
Input Ex ia
Power P 67 mW
Types of measuring 2-, 3-, 4-wire technology
Cold junction compensation external and internal
Types of measuring_1 2-, 3-, 5-wire technology
Rated voltage U 20 ... 30 V DC
Rated current I approx. 100 mA
Display elements LEDs , display
Electromagnetic compatibility NE 21:2007
Marking_1 II 3G Ex nA nC IIC T4 Gc
Collective error message Power Rail
RTD max. 0.2 % of span
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Voltage U 13.1 V
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Certificate PF 08 CERT 1213 X
Output III/power supply and collective error reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Height 119 mm
Current I 21 mA
Thermocouples max. 10µV deviation of CJC: ±0.8 K
Inputs terminals 1, 2, 3, 4, 6 (for passive equipment)
Current output max. 20 µA
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Directive 2014/35/EU EN 61010-1:2010
Width 40 mm
Input_1 terminals 2, 6 (for active equipment)
Connection screw terminals
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Output I, II relay
Load max. 650 Ω
Lead resistance max. 50 Ω
Measurement loop monitoring sensor breakage, sensor short-circuit
Power_1 P 200 mW
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Degree of protection IP20
Mass 300 g
IECEx certificate IECEx TUN 09.0019
Configuration via operating buttons via PACTware
Depth 115 mm
Measurement loop monitoring_1 sensor breakage
Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Temperature effect Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
EU-type examination certificate TÜV 03 ATEX 2140
Connection side control side
Measuring current approx. 400 µA with resistance measuring sensor
Input resistance ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Voltage_1 U 29 V
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
Current range 0 ... 20 mA or 4 ... 20 mA
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Voltage U 13.1 V
Power P 67 mW
Maximum safe voltage_2 U 40 V (Attention! The rated voltage can be lower.) , RS 232
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Current_1 I 11 mA
Safety Integrity Level (SIL) SIL 2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Open loop voltage max. 24 V DC
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Maximum safe voltage_1 U 40 V (Attention! The rated voltage can be lower.)
Sampling rate approx. 700 ms
Maximum safe voltage U 40 V DC (Attention! The rated voltage can be lower.)
Potentiometer 0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩ