商品名称: P+F 倍加福 HiD2030SK SIL-Capable Products for Hazardous Areas Safety Integrity Level 2
品牌名称: P+F 倍加福
分类名称: 安全传感器
商品订货号:
商品型号: HiD2030SK

产品参数
| Mass | 140 g |
| Current | I 93 mA |
| Safety Integrity Level (SIL) | SIL 2 |
| Input/Output | safe electrical isolation acc. to IEC 60079-11:2007, voltage peak value 375 V |
| Labeling | space for labeling at the front |
| Coding | pin 1 and 3 trimmed For further information see system description. |
| Deviation | at 20 °C (68 °F), 0/4 ... 20 mA ≤ 20 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
| Degree of protection | IP20 |
| Directive 2014/34/EU | EN 60079-0:2018 , EN 60079-11:2012 |
| Signal type | Analog input |
| Power dissipation | 350 mW at 24 V, 250 Ω load, 20 mA output (per channel) |
| Connection | SL1: 6b |
| Input current | 4 ... 20 mA , current limit approx. 26 mA typ. |
| Output | sink mode from external supply |
| Maximum safe voltage | U 250 V AC (Attention! U is no rated voltage.) |
| Width | 18 mm |
| Ripple | 10 mV |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Input | Ex ia, Ex iaD |
| Depth | 130 mm |
| Input/power supply | safe electrical isolation acc. to IEC 60079-11:2007, voltage peak value 375 V |
| Input/input | safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V |
| Communication | pass-through of HART signal to safe area The current sink terminals 4, 7 and 5, 6 do not pass HART signal to safe area. |
| EU-type examination certificate | CSANe 21 ATEX 2149 X |
| Connection side | control side |
| Output signal | 4 ... 20 mA |
| Mounting | on termination board |
| Power | P 605 mW |
| Response time | 70 ms , 10 ... 90 % step change |
| Output type | open collector transistor (common to both channels) fault bus signal, collective error message |
| Frequency range | field side into the control side: bandwidth with 0.5 V signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 V signal 0 ... 3 kHz (-3 dB) |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Output/Output | functional insulation, rated insulation voltage 50 V AC |
| IECEx certificate | IECEx CSAE 21.0010X |
| Signal level | no fault: 1 mA ... 23.5 mA input current fault detection: < 0.2 mA or > 24 mA input current |
| Rated current | I 14 mA at 24 V, 250 Ω load, 20 mA output (per channel) |
| Display elements | LEDs |
| Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
| Systematic capability (SC) | SC 3 |
| Input resistance | < 40 Ω , for current source |
| CSA approval | CoC 80072560 (cCSAus) |
| Dimensions | 18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D) |
| Voltage | U 26 V |
| Height | 114 mm |
| Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Relative humidity | 5 ... 90 %, non-condensing up to 35 °C (95 °F) |
| Rated voltage | U 19 ... 30 V DC bus powered via Termination Board |
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Control drawing | 116-0486 |
| Influence of ambient temperature | ≤ 2 µA/K |
| Protection against electrical shock | UL 61010-1:2012 |