商品名称: P+F 倍加福 KFD2-SR2-Ex2.W.SM SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFD2-SR2-EX2.W.SM

KFD2-SR2-EX2.W.SM

产品参数

Labeling space for labeling at the front
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Trip value f for standstill monitoring: 0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz adjustable via DIP switch (S1 and S2)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Contact loading 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Control elements DIP switch
Depth 115 mm
Control drawing_2 116-0047
Safety Integrity Level (SIL) SIL 2
Mass approx. 150 g
Marking_1 II 3G Ex ec nC IIC T4 Gc
Pulse duration > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion
Accuracy 5 % (S3 = I), 30 % (S3 = II)
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate PTB 00 ATEX 2080
Directive 2014/35/EU EN 61010-1:2010
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Programming via DIP switch and programmable
Start-up override 5 seconds or 20 seconds, programmable
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Control drawing 116-0035
Display elements LEDs
Electromagnetic compatibility NE 21:2006
Maximum safe voltage U 253 V AC / 125 V DC (Attention! U is no rated voltage.)
Minimum switch current 2 mA / 24 V DC
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
Control drawing_1 116-0145
Maximum safe voltage_2 U 40 V DC (Attention! U is no rated voltage.)
Rotation direction detection 90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs
Rated voltage U 20 ... 30 V DC
Connection side control side
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
IECEx marking [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc
Width 20 mm
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Signal type Digital Input
Connection screw terminals
Mechanical life 10 switching cycles
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Configuration via DIP switches
Height 119 mm
Maximum safe voltage_1 U 253 V AC (Attention! The rated voltage can be lower.)
UL approval E106378
Rated values acc. to EN 60947-5-6 (NAMUR)
Frequency range ≤ 2 kHz
Degree of protection IP20
Voltage U 10.5 V
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Current I 13 mA
Certificate TÜV 99 ATEX 1493 X
FM certificate FM19US0207X
Control input sensor power supply approx. 8.2 V, impedance 1.2 kΩ
IECEx certificate IECEx PTB 11.0034 , IECEx TUN 19.0013X
Input Ex ia
Power P 34 mW (linear characteristic)
Power consumption max. 1.5 W