买道传感网

分类

商品名称: P+F 倍加福 S1SD-1FI-1R 信号调节器 SC-System (DIN rail, compact design)

品牌名称: P+F 倍加福

分类名称: 模块

商品订货号:

商品型号: S1SD-1FI-1R

S1SD-1FI-1R

产品参数

Labeling space for labeling at the front
Dimensions 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1
Height 97 mm
Type_1 2-wire
Connection_1 terminals 5+, 6
External supply ≤ 32 V
External supply_2 ≤ 32 V
Switching point_7 150 ... 400 mV
Input impedance_8 approx. 50 kΩ
Switching point_9 > 12 V , edge triggered
Frequency range 0.01 ... 50000 Hz
Display elements LEDs
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Connection_3 terminals 5+, 6
Signal_1 acc. to EN 60947-5-2
Sensor supply_3 16 V / 25 mA , short-circuit protected
Connection_4 terminals 5+, 6
Connection_5 terminals 5+, 6, 7-
Open loop voltage 7.5 V
Power dissipation 0.6 W
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Measuring time ≤ 100 ms
Short-circuit > 6 mA
Type_4 2-wire
Input impedance_4 4 kΩ
Signal_3 acc. to EN 60947-5-2
Switching point_5 3 ... 5 V
Signal_4 acc. to EN 60947-5-2
Sensor supply_6 16 V / 25 mA , short-circuit protected
External supply_3 ≤ 32 V
Switching point_6 8 ... 10 V
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load
Function 2 reset restart inhibit
Rated voltage U 16.8 ... 31.2 V DC
Power consumption 1.1 W
Protection against electrical shock EN 61010-1:2010
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Input/Other circuits safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V test voltage 3 kV, 50 Hz, 1 min
Input impedance 1 kΩ
Sensor supply_4 15 V
Switching point_4 0.15 ... 2 mA
Connection_6 terminals 5+, 6, 7-
Minimum switch current 2 mA / 24 V DC
Function 1 activation start-up override
Connection screw terminals
Mass approx. 60 g
Accuracy max. 0.1 % of the measurement value
Sensor supply_1 15 V
Switching point_2 1.2 ... 2.1 mA
Type_5 3-wire
Sensor supply_5 16 V / 25 mA , short-circuit protected
Input impedance_6 4 kΩ
Mechanical life 10 switching cycles
Output/power supply safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V test voltage 3 kV, 50 Hz, 1 min
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Core cross section 0.5 ... 2.5 mm (20 ... 14 AWG)
Sensor supply_2 8 V
Short-circuit_1 > 6 mA
Directive 2014/35/EU EN 61010-1:2010
Influence of ambient temperature < 100 ppm/K of the measured value
Open-circuit_1 < 0.1 mA
Connection_7 terminals 6, 7-
Signal_5 max. ± 30 V
Signal type Digital Input
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Programming interface programming socket
Switching point 1.2 ... 2.1 mA
Connection_2 terminals 5+, 6
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Connection side control side
Width 6.2 mm
Depth 107 mm
Signal acc. to EN 60947-5-6 (NAMUR)
Sensor supply 8 V
Switching point_1 8 ... 10 V / 1.2 ... 2.1 mA
Type_2 2-wire
Type_3 2-wire
External supply_1 ≤ 32 V
Input impedance_3 1 kΩ
Signal_2 acc. to EN 62053-31 , Type B
Input impedance_5 4 kΩ
Type_6 3-wire
Switching point_8 < 3 V , edge triggered
Output signal, relay
Degree of protection IP20
Configuration via DIP switches via software
Type 2-wire
Open-circuit < 0.1 mA
Input impedance_1 4 kΩ
Input impedance_2 1 kΩ
Switching point_3 2 ... 5 mA
Input impedance_7 4 kΩ
Connection_8 terminal 8
Frequency 0 ... 50 Hz , debounce filter
Adjustment range 1 ... 6500 s

相关资料