商品名称: P+F 倍加福 HiD2824 SIL-Capable Products for Hazardous Areas Safety Integrity Level 2
品牌名称: P+F 倍加福
分类名称: 安全传感器
商品订货号:
商品型号: HID2824

产品参数
| Dimensions | 18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D) |
| Signal type | Digital Input |
| Display elements | LEDs |
| Height | 114 mm |
| Width | 18 mm |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms |
| Protection against electrical shock | UL 61010-1:2012 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Mass | approx. 140 g |
| Connection side | control side |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
| Output type | open collector transistor (internal fault bus) |
| Degree of protection | IP20 |
| Voltage | U 13.2 V |
| Output/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V |
| Power | P 66 mW |
| Connection | SL1: 6b |
| Labeling | space for labeling at the front |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Control elements | DIP switch |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Factory setting | input closed, relay energized, lead fault detection enabled |
| EU-type examination certificate | CESI 21 ATEX 017 |
| Current | I 20 mA |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Safety Integrity Level (SIL) | SIL 2 |
| Rated current | I 60 mA at 24 V, relay energized |
| Control drawing | 116-0487 (cCSAus) |
| Power dissipation | 1.45 W at 24 V |
| Switching frequency | < 10 Hz |
| Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 For further information see system description. |
| Contact loading | 50 V DC / 0.5 A non-inductive |
| Maximum safe voltage | U 250 V AC (Attention! U is no rated voltage.) |
| IECEx certificate | IECEx CES 21.0011 |
| Input | Ex ia |
| Response time | 20 ms |
| Coding | pin 1 and 2 trimmed For further information see system description. |
| CSA approval | CoC 80097459 (cCSAus) |
| Rated voltage | U 19 ... 30 V DC bus powered via Termination Board |
| Mechanical life | 10 switching cycles |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
| Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
| Configuration | via DIP switches |
| Depth | 130 mm |
| Mounting | on termination board |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-11:2012 |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Output | signal: relay SPST per channel, phase selectable |
| Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V |
| Input/input | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 60 V |