商品名称: P+F 倍加福 S1SL-1AI-1C 信号调节器 SC-System (DIN rail, compact design)
品牌名称: P+F 倍加福
分类名称: 其他过程测量仪表
商品订货号:
商品型号: S1SL-1AI-1C

产品参数
| Power dissipation | 0.05 W |
| Connection side | control side |
| Height | 97 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
| Ripple | ≤ 10 mV |
| Influence of ambient temperature | < 100 ppm/K of full-scale value |
| Labeling | space for labeling at the front |
| Voltage drop | ≤ 2.3 V |
| Core cross section | 0.5 ... 2.5 mm (20 ... 14 AWG) |
| Power consumption | 0.3 W |
| Degree of protection | IP20 |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Depth | 107 mm |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Analog current output | 0/4 ... 20 mA, load ≤ 600 Ω |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Input signal | 0/4 ... 20 mA , max. 50 mA |
| Accuracy | max. 0.1 % of full-scale value |
| Field circuit/control circuit | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V test voltage 3 kV, 50 Hz, 1 min |
| IECEx certificate | IECEx UL 16.0116X |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Rated voltage | U 2.2 ... 30 V DC , loop powered |
| Frequency range | 0 ... 100 Hz |
| Width | 6.2 mm |
| Certificate | DEMKO 16 ATEX 1750X |
| Rise time/fall time | ≤ 3.5 ms |
| Protection against electrical shock | EN 61010-1:2010 |
| Mass | approx. 70 g |
| UL approval | E106378 |
| Connection | screw terminals |
| Operation time | MTBF: 2865 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F) |
| Marking | II 3G Ex nA IIC T4 Gc |
| Input voltage | ≥ 2.3 V + I x load , max. 30 V |
| Signal type | Analog input |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1 |
| Influence of load | 0.05 % of the measured value per 100 Ω |
| IECEx marking | Ex nA IIC T4 Gc |