Rated voltage U 19 ... 30 V DC
Labeling space for labeling at the front
Electromagnetic compatibility NE 21:2006
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Connection side control side
Maximum safe voltage U 253 V AC (Attention! The rated voltage can be lower.)
Current range 4 ... 20 mA , (source or sink mode)
Height 119 mm
Control drawing 116-0129
Signal type Analog input
Load max. 650 Ω , source mode
Current I 104.9 mA
Accuracy < 20 µA, 10 µA typ.
Output I, II/other circuits reinforced insulation acc. to IEC 62103, rated insulation voltage 300 V
Maximum safe voltage_2 U 253 V (Attention! U is no rated voltage.)
Other outputs HART communicator on terminals 22, 24
Connection screw terminals
Contact loading 253 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (BASEEFA 07 ATEX 0174) 50 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (Pepperl+Fuchs self-declaration)
Configuration via operating buttons via PACTware
IECEx certificate IECEx BAS 07.0047
Depth 115 mm
Marking_1 II 3G Ex nA nC IIC T4 Gc
Collective error message Power Rail and LED red
Available voltage ≥ 15.5 V at 20 mA, short-circuit protected
Power_1 P < 1.33 W
Internal capacitance_1 C 0 µF
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC
Rated current I approx. 130 mA at 24 V DC
Open circuit voltage/short-circuit current typ. 24 V / 28 mA
Equipment_1 terminals 2, 5/3
Fault signal downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value
Display elements LEDs , display
Mass 300 g
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Certificate PF 07 CERT 1141 X
EU-type examination certificate BASEEFA 07 ATEX 0174
Voltage U 25.2 V
Influence of ambient temperature < ± 2 µA/K
Internal capacitance C 1.1 nF
Relay programmable either for fault or trip value (with direction, hysteresis and delay)
Output III/IV/V/power supply functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Power P 0.661 W
Duration of measurement/Response delay HART message acquisition time plus 100 ms
Voltage_1 U < 28 V
Current_1 I 11.9 mA
Power dissipation 2.5 W
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Directive 2014/35/EU EN 61010-1:2010
Mechanical life 10 switching cycles
Maximum safe voltage_1 U 253 V (Attention! U is no rated voltage.)
Power consumption 3.1 W
Output I, II terminals 10, 11, 12; 16, 17, 18 , non-intrinsically safe
Output signal relay and LED yellow
Equipment terminals 1, 4/3 (with link between terminals 4 and 5)
Internal inductance L 0 mH
Internal inductance_1 L 0 mH
Output III, IV, V terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe
Voltage range 5 ... 30 V , sink mode from external supply
Width 40 mm
Input resistance 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6)
Resolution max. 2 µA
Voltage_2 U 1.1 V
Control elements Control panel
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Degree of protection IP20
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC
Programming interface programming socket
Conformity HART field device input (revision 5 to 7)
Power_2 P 4 mW
Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output signal_1 analog
Output I/II functional insulation acc. to IEC 62103, rated insulation voltage 250 V