产品参数
| Rated voltage | U 19 ... 30 V DC |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | NE 21:2006 |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
| Connection side | control side |
| Maximum safe voltage | U 253 V AC (Attention! The rated voltage can be lower.) |
| Current range | 4 ... 20 mA , (source or sink mode) |
| Height | 119 mm |
| Control drawing | 116-0129 |
| Signal type | Analog input |
| Load | max. 650 Ω , source mode |
| Current | I 104.9 mA |
| Accuracy | < 20 µA, 10 µA typ. |
| Output I, II/other circuits | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 V |
| Maximum safe voltage_2 | U 253 V (Attention! U is no rated voltage.) |
| Other outputs | HART communicator on terminals 22, 24 |
| Connection | screw terminals |
| Contact loading | 253 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (BASEEFA 07 ATEX 0174) 50 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (Pepperl+Fuchs self-declaration) |
| Configuration | via operating buttons via PACTware |
| IECEx certificate | IECEx BAS 07.0047 |
| Depth | 115 mm |
| Marking_1 | II 3G Ex nA nC IIC T4 Gc |
| Collective error message | Power Rail and LED red |
| Available voltage | ≥ 15.5 V at 20 mA, short-circuit protected |
| Power_1 | P < 1.33 W |
| Internal capacitance_1 | C 0 µF |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC |
| Rated current | I approx. 130 mA at 24 V DC |
| Open circuit voltage/short-circuit current | typ. 24 V / 28 mA |
| Equipment_1 | terminals 2, 5/3 |
| Fault signal | downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value |
| Display elements | LEDs , display |
| Mass | 300 g |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Certificate | PF 07 CERT 1141 X |
| EU-type examination certificate | BASEEFA 07 ATEX 0174 |
| Voltage | U 25.2 V |
| Influence of ambient temperature | < ± 2 µA/K |
| Internal capacitance | C 1.1 nF |
| Relay | programmable either for fault or trip value (with direction, hysteresis and delay) |
| Output III/IV/V/power supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 V |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Power | P 0.661 W |
| Duration of measurement/Response delay | HART message acquisition time plus 100 ms |
| Voltage_1 | U < 28 V |
| Current_1 | I 11.9 mA |
| Power dissipation | 2.5 W |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Directive 2014/35/EU | EN 61010-1:2010 |
| Mechanical life | 10 switching cycles |
| Maximum safe voltage_1 | U 253 V (Attention! U is no rated voltage.) |
| Power consumption | 3.1 W |
| Output I, II | terminals 10, 11, 12; 16, 17, 18 , non-intrinsically safe |
| Output signal | relay and LED yellow |
| Equipment | terminals 1, 4/3 (with link between terminals 4 and 5) |
| Internal inductance | L 0 mH |
| Internal inductance_1 | L 0 mH |
| Output III, IV, V | terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe |
| Voltage range | 5 ... 30 V , sink mode from external supply |
| Width | 40 mm |
| Input resistance | 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6) |
| Resolution | max. 2 µA |
| Voltage_2 | U 1.1 V |
| Control elements | Control panel |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Degree of protection | IP20 |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC |
| Programming interface | programming socket |
| Conformity | HART field device input (revision 5 to 7) |
| Power_2 | P 4 mW |
| Input/Other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Output signal_1 | analog |
| Output I/II | functional insulation acc. to IEC 62103, rated insulation voltage 250 V |