买道传感网

分类

商品名称: P+F 倍加福 KFD2-DWB-Ex1.D SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFD2-DWB-EX1.D

KFD2-DWB-EX1.D

产品参数

Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Directive 2014/35/EU EN 61010-1:2010
IECEx certificate IECEx TUN 03.0000 IECEx TSA 18.0007X
Input frequency 0.001 ... 5000 Hz
Input I/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Control elements Control panel
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Control drawing 16-538FM-12
Mechanical life 5 x 10 switching cycles
Marking_1 II 3G Ex nA nC IIC T4 Gc
Pulse duration > 50 µs
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Contact loading_1 50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Collective error message Power Rail
Width 40 mm
Voltage U 10.1 V
Maximum safe voltage U 40 V (Attention! The rated voltage can be lower.)
UL approval E223772
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Signal type Digital Input
Connection side control side
Connection screw terminals
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Degree of protection IP20
Mass 300 g
EU-type examination certificate TÜV 99 ATEX 1408
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Maximum safe voltage U 40 V DC (Attention! U is no rated voltage.)
Certificate TÜV 02 ATEX 1885 X
Measuring range 0.001 ... 5000 Hz
Accuracy 0.1 % of measured value , > 0.001 Hz
Measuring time < 100 ms
Response delay ≤ 200 ms
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Rated voltage U 20 ... 30 V DC
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec nC IIC T4 Gc
Resolution 0.1 % of measured value , ≥ 0.001 Hz
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Electromagnetic compatibility NE 21:2006
Input II terminals 13+, 14- non-intrinsically safe
Open circuit voltage/short-circuit current 18 V / 5 mA
Depth 115 mm
Maximum safe voltage_1 U 253 V (Attention! The rated voltage can be lower.)
Rated current I approx. 100 mA
Input I terminals 1+, 3-: Ex ia
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Influence of ambient temperature 0.003 %/K (30 ppm)
Start-up override/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Configuration via operating buttons
Power P 34 mW (linear characteristic)
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Power dissipation/power consumption ≤ 1.8 W / 1.8 W
Height 119 mm
Current I 13.5 mA
Safety Integrity Level (SIL) SIL 2
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Display elements LEDs , display
Labeling space for labeling at the front
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

相关资料