买道传感网

分类

商品名称: P+F 倍加福 M-LB-2144 Surge Protection Barriers 用于信号线保护的设备

品牌名称: P+F 倍加福

分类名称: 电涌保护器

商品订货号:

商品型号: M-LB-2144

M-LB-2144

产品参数

Maximum continuous operating voltage U 30 V DC
Insertion loss ≤ 3 dB at 0 ... 700 kHz in 100 Ω system
Corrosion resistance acc. to ISA-S71.04, severity level G3
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Connection screw terminals , max. core cross section 1 x 2.5 mm
Rated current I 500 mA , restrictions see derating tables UL : 400 mA , restrictions see derating tables
Nominal discharge current (8/20 µs) I 5 kA per line (10x)
Voltage protection level U max. 45 V line-line for nominal discharge current I max. 60 V line-earth for nominal discharge current I
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Impulse rating 1 kV/0.5 kA (category C1) 10 kV/5 kA (category C2) 1 kA (category D1)
Functional safety IEC/EN 61508:2010
Surge protective devices for low voltage IEC 61643-21:2000+A1:2008+A2:2012
Temperature class T6, T5 or T4 , restrictions see derating tables
Series resistance ≤ 3 Ω per line
Impulse reset time < 500 ms
Depth 72.4 mm
Certificate KIWA 19 ATEX 0002 X
UL approval E501704 E501881
Breakdown voltage U 30 ... 45 V line-line at 100 V/s acc. to UL 497B 30 ... 45 V line-earth at 100 V/s acc. to UL 497B < 1000 V at 100 V/µs acc. to UL 497B
IECEx certificate IECEx KIWA 19.0002X
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018
Topology grounded
Leakage current < 6 µA at 24 V and 25 °C (77 °F) , line-line
Degree of protection IP20 , after mounting of the insulation spacer
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Relative humidity max. 95 % , without condensation
Electromagnetic compatibility EN 61326-3-1:2017
Material Polyamide (PA)
Height 93 mm
IECEx marking Ex ec IIC T6...T4 Gc
Impulse discharge current (10/350 µs) I 1 kA per line (2x)
Ambient temperature -40 ... 80 °C (-40 ... 176 °F) Observe the temperature range limited by derating, see section derating.
Marking II 3G Ex ec IIC T6...T4 Gc
Total discharge current (8/20 µs) I 20 kA (1x) , overstressed fault mode 3 acc. to IEC 61643-21
Number of protected signal lines 2
Mass approx. 32 g
Nominal voltage 24 V DC
Dimensions 6.2 x 93 x 72.4 mm (0.24 x 3.7 x 2.8 inch) (W x H x D)
Safety Integrity Level (SIL) SIL 3
Width 6.2 mm