产品参数

Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
UL approval E223772
Directive 2014/35/EU EN 61010-1:2010
Rated current I approx. 100 mA
Output I, II signal, relay
Collective error message Power Rail
Influence of ambient temperature_1 0.005 %/K (50 ppm)
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Load max. 650 Ω
Degree of protection IP20
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-15:2010
Configuration via operating buttons via PACTware
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Interface/output III basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Connection screw terminals
Electromagnetic compatibility NE 21:2006
Ambient temperature -20 ... 50 °C (-4 ... 122 °F)
Switching point/switching hysteresis logic 1: > 2.5 mA ; logic 0: < 1.9 mA
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Height 119 mm
Certificate PF 08 CERT 1216 X
Measuring time < 100 ms
Contact loading_1 40 V DC
Current range 0 ... 20 mA or 4 ... 20 mA
Signal type Digital Input
Programming interface programming socket
Response delay ≤ 200 ms
Output III/power supply and collective error basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Output III/IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Input resistance 4.7 kΩ
Mass 300 g
Depth 115 mm
Marking II 3G Ex nA nC IIC T4 Gc
Fault signal downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Power dissipation/power consumption ≤ 2 W / 2.2 W
Input frequency 0.001 ... 10000 Hz
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Open circuit voltage/short-circuit current_1 18 V / 5 mA
Output III electronic output, passive
Output IV/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Connection side control side
Labeling space for labeling at the front
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Measuring range 0.001 ... 10000 Hz
Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Mechanical life 5 x 10 switching cycles
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)
Open loop voltage max. 24 V DC
Rated voltage U 20 ... 30 V DC
Open circuit voltage/short-circuit current 22 V / 40 mA
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Accuracy 0.1 % of the measurement value , > 0.001 Hz
Input I 2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Resolution 0.1 % of the measurement value , ≥ 0.001 Hz
Resolution_1 < 10 µA
Accuracy_1 < 20 µA
Interface/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Display elements LEDs , display
Width 40 mm
Pulse duration > 50 µs
Start-up override/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Safety Integrity Level (SIL) SIL 2
Influence of ambient temperature 0.003 %/K (30 ppm)
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Output IV analog