买道传感网

分类

商品名称: P+F 倍加福 KFU8-CRG2-Ex1.D SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

品牌名称: P+F 倍加福

分类名称: 安全传感器

商品订货号:

商品型号: KFU8-CRG2-Ex1.D

KFU8-CRG2-Ex1.D

产品参数

Rated voltage U 20 ... 90 V DC or 48 ... 253 V AC
Maximum safe voltage U 253 V AC (Attention! The rated voltage can be lower.)
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Output III/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Equipment_2 terminals 1+, 2 / 3-
Current_3 I 112 mA
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
EU-type examination certificate TÜV 01 ATEX 1701
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 01 ATEX 1701)
IECEx certificate IECEx TUN 09.0007
Accuracy < 30 µA
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Width 40 mm
Interface RS 232
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Connection side control side
Mechanical life 5 x 10 switching cycles
Voltage_2 U 5 V
Current_1 I 115 mA
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Connection screw terminals
Labeling space for labeling at the front
Line fault detection breakage I < 0.2 mA; short-circuit I > 22 mA
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Influence of ambient temperature 0.003 %/K (30 ppm)
Response delay ≤ 200 ms at bounce from 0 ... 20 mA
Configuration via operating buttons via PACTware
Input Ex ia
Input/Other circuits safe galvanic isolation acc. to EN 50020, voltage peak value 375 V
Safety Integrity Level (SIL) SIL 2
Degree of protection IP20
Equipment terminals 1+, 3-
Power_2 P 720 mW
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Voltage U 25.8 V
Power dissipation 2 W / 3 VA
Directive 2014/35/EU EN 61010-1:2010
Current I 93 mA
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Open circuit voltage/short-circuit current 24 V / 33 mA
Output III terminals 8+, 7- non-intrinsically safe
Load max. 650 Ω
Available voltage > 15 V at 20 mA
Voltage_1 U < 30 V
Voltage_3 U 25.8 V
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Signal type Analog input
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Programming interface programming socket
Accuracy_1 < 20 µA
Influence of ambient temperature_1 0.005 %/K (50 ppm)
Depth 115 mm
Input signal 0/4 ... 20 mA
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Maximum safe voltage U U 40 V (Attention! The rated voltage can be lower.)
Power P 0.603 W
Input resistance 45 Ω (terminals 2, 3)
Power_1 P 0.3 mW
Control drawing 16-554FM-12 (cFMus)
Energized/De-energized delay 0 ... 250 s , adjustable
Display elements LEDs , display
Control elements Control panel
Maximum safe voltage_1 U 253 V AC / 40 V DC (Attention! U is no rated voltage.)
Reaction time < 650 ms at bounce from 0 ... 20 mA at the input, 90 % of output full-scale value
Equipment_1 terminals 2-, 3
Mass 300 g
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012
Electromagnetic compatibility NE 21:2006
Current range 0 ... 20 mA or 4 ... 20 mA
Open loop voltage max. 24 V DC
Resolution ≤ 10 µA
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Height 119 mm
Maximum safe voltage_2 U 40 V (Attention! The rated voltage can be lower.) , RS 232
Power consumption 2.2 W / 4 VA
Output signal 0 ... 20 mA or 4 ... 20 mA
Current_2 I 0.3 mA