买道传感网

分类

商品名称: P+F 倍加福 K-LB-2.30 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

品牌名称: P+F 倍加福

分类名称: 其他(中低压配电)

商品订货号:

商品型号: K-LB-2.30

K-LB-2.30

产品参数

Dimensions 12.5 x 115 x 116 mm (0.5 x 4.5 x 4.6 inch) (W x H x D)
IECEx certificate IECEx BAS 14.0010X
Internal capacitance C negligible
Internal inductance L 200 µH
Leakage current < 5 µA at 24 V and 25 °C (77 °F) , line-line
Marking II 2(1)G Ex ia IIC T6/T5/T4
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012
Nominal discharge current (8/20 µs) I 5 kA per line (10x)
Rated surge current (8/20 µs) I 10 kA per line (1x)
Ambient temperature -30 ... 80 °C (-22 ... 176 °F) For usage in hazardous area observe the EC-type examination certificate.
Topology non-grounded
Series resistance < 0.5 Ω per line
Safety Integrity Level (SIL) SIL 3
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Maximum continuous operating voltage U 30 V DC
Mounting location indoor
Number of protected signal lines 4
Width 12.5 mm
Mass approx. 100 g
EU-type examination certificate PTB 00 ATEX 2176 X
Current I 250 mA
Depth 116 mm
Impulse discharge current (10/350 µs) I 2 kA per line (2x)
Surge protective devices for low voltage EN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012
Rated current I 250 mA
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Height 115 mm
Voltage protection level U max. 75 V line-line for nominal discharge current I max. 1.2 kV line-earth for nominal discharge current I
Voltage U 30 V
Certificate PF 16 CERT 4065 X
Nominal voltage 24 V DC
Impulse reset time < 30 ms
Insertion loss ≤ 0.05 dB, at 0 ... 4 kHz, in 600 Ω-System ≤ 3 dB, at 0 ... 174 kHz, in 100 Ω-System
Relative humidity 5 ... 95 %
Degree of protection IP20
Marking_1 II (3)D [Ex ic Dc] IIIC
Total discharge current (8/20 µs) I 20 kA (1x)
Control drawing 116-0187 (cCSAus)
Connection screw terminals
Labeling space for labeling at the front
Impulse rating 10 kV/5 kA (category C2) 2 kV/2 kA (category D1)
Core cross section 2 x 2.5 mm
Temperature class T6 for ambient temperature ≤ 50 °C T5 for ambient temperature ≤ 70 °C T4 for ambient temperature ≤ 80 °C