买道传感网

分类

安全传感器-视觉传感器/安全传感器-安全传感器品牌厂家-买道传感网官网

P+F 倍加福 P-LB-1.A.13 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

商品名称: P+F 倍加福 P-LB-1.A.13 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

商品型号: P-LB-1.A.13

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 安全栅

Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Marking_1 II 3G Ex nA IIC T4 Gc
Asymmetric 100 ns
IECEx certificate IECEx BAS 12.0123
Rated voltage U max. 30 V
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Series resistor ≤ 0.5 Ω per wire
Rated current I max. 250 mA
Ground insulation max. 500 V breakdown voltage
Degree of protection IP20
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Dimensions 20 x 104 x 127 mm (0.8 x 4.1 x 5 inch) (W x H x D)
Current I 250 mA
On-state voltage max. 45 V
Mounting on the KF module
Bandwidth ≥ 40 kHz
Marking II (1)G [Ex ia Ga] IIC
Internal capacitance C negligible
Internal inductance L 200 µH
Safety Integrity Level (SIL) SIL 3
Voltage U 30 V
Connection terminals 1, 3
Leakage current max. 5 µA
EU-type examination certificate PTB 02 ATEX 2044
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Number of protected signal lines 2
Mass approx. 70 g
Symmetrical 1 ns
Labeling space for labeling at the front
Certificate PF 16 CERT 3908 X
Maximum leakage current 10 kA (8/20 µs) per conductor
P+F 倍加福 S1SD-1TI-1U 信号调节器 SC-System (DIN rail, compact design)

商品名称: P+F 倍加福 S1SD-1TI-1U 信号调节器 SC-System (DIN rail, compact design)

商品型号: S1SD-1TI-1U

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 隔离栅

Rated voltage U 16.8 ... 31.2 V DC
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mass approx. 70 g
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accuracy max. 0.1 % of full-scale value
Certificate DEMKO 16 ATEX 1750X
Measurement loop monitoring sensor breakage, lead breakage, short circuit
Power dissipation 0.7 W
Operation time MTBF: 353 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F)
Lead resistance ≤ 100 Ω per line
Fault signal downscale or upscale
Measuring time ≤ 300 ms
Ripple ≤ 10 mV
Power consumption 0.8 W
Connection side control side
RTD < 0.1 K/0.05 % of the measured value
Voltage < 0.1 % of the measured value
Signal type Analog input
Input resistance ≥ 1 MΩ
Influence of ambient temperature < 100 ppm/K of full-scale value
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Marking II 3G Ex nA IIC T4 Gc
Programming interface programming socket
IECEx certificate IECEx UL 16.0116X
Measuring current_1 approx. 200 µA
Measurement loop monitoring_1 sensor breakage, lead breakage, short circuit
Height 97 mm
Core cross section 0.5 ... 2.5 mm (20 ... 14 AWG)
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-15:2010
UL approval E106378
PTC type KT, KTY, ST
Types of measuring 2-, 3-, 4-wire connection
Connection screw terminals
Protection against electrical shock EN 61010-1:2010
Dimensions 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1
Width 6.2 mm
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Measuring current approx. 200 µA
Measurement loop monitoring_2 sensor breakage, lead breakage
Types of measuring_2 3-wire connection
Analog voltage output 0/1 ... 5 V , 0/2 ... 10 V , load ≥ 2 kΩ
Types of measuring_1 2-, 3-, 4-wire connection
Cold junction compensation external (Pt100) and internal , manually
Potentiometer < 0.02 % of the measured value
Input/Other circuits safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V test voltage 3 kV, 50 Hz, 1 min
Output/power supply safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V test voltage 3 kV, 50 Hz, 1 min
Analog current output 0/2 ... 10 mA, 0/4 ... 20 mA, load ≤ 600 Ω
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
IECEx marking Ex nA IIC T4 Gc
Configuration via DIP switches via keys via software
Labeling space for labeling at the front
Degree of protection IP20
Depth 107 mm
Lead resistance_1 max. 100 Ω per line
Thermocouples < 0.3 K/0.1 % of the measured value
Lead resistance_2 max. 10 kΩ
Measuring range 0 ... 5 kΩ
P+F 倍加福 HiD2038 SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

商品名称: P+F 倍加福 HiD2038 SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

商品型号: HID2038

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 隔离栅

Mounting on termination board
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
IECEx certificate IECEx ULD 20.0012X
Line fault detection breakage, load > 100 kΩ, short-circuit, load < 50 Ω
Width 18 mm
Power consumption ≤ 1 W
Rated voltage U 19 ... 30 V DC bus powered via Termination Board
Dimensions 18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Connection side field side
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Electromagnetic compatibility NE 21:2017 EN 61326-3-2:2018 For further information see system description.
Output Ex ia, Ex iaD
Current I 93 mA
Depth 130 mm
Maximum safe voltage_1 U 250 V (Attention! The rated voltage can be lower.)
Input/input functional insulation, rated insulation voltage 50 V AC
Degree of protection IP20
Mass approx. 140 g
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Power dissipation ≤ 1 W at 20 mA and 500 Ω load
Output type open collector transistor (internal fault bus)
Coding pin 1 and 3 trimmed For further information see system description.
EU-type examination certificate DEMKO 20 ATEX 2378 X
Certificate DEMKO 20 ATEX 2379 X
Marking_1 II 3G Ex ec IIC T4 Gc
Internal capacitance C 1.05 nF
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018
Input voltage open loop voltage of the control system ≤ 30 V
Labeling space for labeling at the front
Maximum safe voltage U 250 V (Attention! The rated voltage can be lower.)
Influence of ambient temperature < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
Output/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Protection against electrical shock UL 61010-1:2012
Deviation at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis
Frequency range field side into the control side: bandwidth with 0.5 V signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 V signal 0 ... 3 kHz (-3 dB)
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Voltage U 25.2 V
Connection SL1: 6b
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc
Load 100 ... 650 Ω , for terminals 1a, 1b; 5a, 5b 0 ... 550 Ω , for terminals 1b, 3b; 5b, 7a
UL approval E106378
Voltage drop approx. 6 V at 20 mA
Input signal 4 ... 20 mA , limited to approx. 30 mA
Rated current I ≤ 40 mA at 24 V
Rise time 10 to 90 % ≤ 10 ms
Power P 585.3 mW
Input/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Internal inductance L 0
Safety Integrity Level (SIL) SIL 2
Control drawing 116-0475 (cULus)
Signal type Analog output
Display elements LEDs
Height 114 mm
Ripple 20 mV rms
Input resistance field wiring open circuit : > 100 kΩ field wiring < 50 Ω : > 100 kΩ when using terminals 5a, 5b; 1a, 1b
P+F 倍加福 HiD2872 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

商品名称: P+F 倍加福 HiD2872 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

商品型号: HiD2872

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 隔离栅

Display elements LEDs
Signal level 1-signal: 15...30 V DC (current limited to 3 mA) or contact close (internal 10 kΩ pull-up) 0-signal: 0...5 V DC or contact open
Open loop voltage U approx. 22.5 V
EU-type examination certificate CESI 10 ATEX 036
Energized/De-energized delay - bus powered: filter OFF: 1 ms, filter ON: 10 ms - loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load)
Internal resistor R approx. 240 Ω
Fault current 4 mA pulsing (20 ms ON, 200 ms OFF)
Mass approx. 140 g
Dimensions 18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Voltage U 26 V
Output Ex ia Ga, Ex ia Da, Ex ia Ma
IECEx certificate IECEx CES 10.0013
Depth 130 mm
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mounting on termination board
Switching frequency f - bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz - loop powered: max. 10 Hz
Certificate PF 10 CERT 1729 X
Current limit I 55 mA
Rated voltage U 20.4 ... 30 V DC loop powered 20.4 ... 30 V DC bus powered via Termination Board
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Input current 62 mA at 24 V, 300 Ω load (per channel)
Current I 110 mA
Output type open collector transistor (internal fault bus)
Coding pin 1 and 4 trimmed For further information see system description.
Safety Integrity Level (SIL) SIL 3
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Control drawing 366-005CS-12B (cCSAus)
Labeling space for labeling at the front
Height 114 mm
Connection side field side
Connection SL1: 6b
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Marking_1 II 3G Ex nA IIC T4 Gc
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Power P 715 mW
Output/Output safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
Electromagnetic compatibility NE 21:2006 For further information see system description.
Configuration via DIP switches
Width 18 mm
Control input external switch (dry contact or open collector) non isolated or logic signal input fully floating
Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Signal type Digital Output
Power dissipation 1 W at 24 V, 300 Ω load (per channel) for loop powered
Maximum safe voltage U 253 V AC (Attention! U is no rated voltage.)
Control elements DIP switch
Inrush current 0.2 A , 15 ms loop powered
Fault level lead short-circuit detection at < 25 Ω lead breakage detection at > 100 kΩ typical
Output/power supply, inputs, and collective error safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Degree of protection IP20
Load nominal 0.1 ... 5 kΩ
P+F 倍加福 HiC2031HC SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

商品名称: P+F 倍加福 HiC2031HC SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

商品型号: HiC2031HC

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 安全栅

Safety Integrity Level (SIL) SIL 2
Input voltage depending on switch configuration open loop voltage of the control system < 19 V open loop voltage of the control system < 26 V
Height 106 mm
Equipment SL2: 5a(+), 5b(-)
Internal inductance L negligible
Dimensions 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Influence of ambient temperature < 2 µA/K (0 ... 60 °C (32 ... 140 °F)); < 4 µA/K (-20 ... 0 °C (-4 ... 32 °F))
Power consumption ≤ 700 mW
Frequency range field side into the control side: bandwidth with 0.5 V signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 1 mA signal 0 ... 3 kHz (-3 dB)
Mass approx. 100 g
Labeling space for labeling at the front
Maximum safe voltage U 253 V AC (Attention! U is no rated voltage.)
Voltage drop depending on switch configuration open loop voltage of the control system < 19 V: approx. 5 V at 20 mA open loop voltage of the control system < 26 V: approx. 12 V at 20 mA
Power P 500 mW
Factory setting input: max. input voltage 19 V
Rated current I ≤ 35 mA
Power dissipation ≤ 600 mW
Connection side field side
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Maximum safe voltage_1 U 253 V AC (Attention! The rated voltage can be lower.)
Input signal 4 ... 20 mA , limited to approx. 27 mA
Ripple 20 mV rms
Rated voltage U 19 ... 30 V DC bus powered via Termination Board
Configuration via DIP switches
Depth 128 mm
Degree of protection IP20
Control drawing 116-0393 (cULus)
Signal type Analog output
Output Ex ia
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Width 12.5 mm
Internal capacitance C 5.7 nF
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Current I 100 mA
Certificate CESI 19 ATEX 050 X
Input resistance > 100 kΩ, with field wiring open
Mounting on termination board
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Electromagnetic compatibility NE 21:2012 For further information see system description.
Marking_1 II 3G Ex ec IIC T4 Gc
Control elements DIP switch
Rise time 10 to 90 % ≤ 100 ms
Coding pin 2 and 4 trimmed For further information see system description.
Deviation at 20 °C (68 °F), 4 ... 20 mA ≤ ± 0.1 % incl. non-linearity and hysteresis
EU-type examination certificate CESI 11 ATEX 012
Voltage U 20 V
Connection SL2: 5a(+), 5b(-)
Display elements LED
IECEx certificate IECEx CES 11.0010X
Load 0 ... 625 Ω
UL approval E106378
Systematic capability (SC) SC 3
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
P+F 倍加福 HiC2851 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

商品名称: P+F 倍加福 HiC2851 SIL-Capable Products for Hazardous Areas Safety Integrity Level 3

商品型号: HIC2851

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 隔离栅

Degree of protection IP20
Mounting on termination board
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Height 106 mm
Depth 128 mm
Output II ≤ 50 Hz
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Lead resistance max. 50 Ω , consider capacitances and inductances
Switching point 1-signal: I > 2.8 mA 0-signal: I < 2.1 mA
Rated current I ≤ 55 mA
IECEx certificate IECEx BAS 07.0097X
Rated voltage U output II: typ. 8 V DC, max. 22 V DC
Dimensions 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Labeling space for labeling at the front
Line fault detection breakage I ≤ 0.15 mA , short-circuit I ≥ 8.5 mA
Ripple ≤ 10 %
Output I ≤ 50 Hz
Voltage U 10.5 V
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
Current I 17.1 mA
Marking II (1)G [Ex ia] IIC , [exsign] II (1) D [Ex ia] IIIC , [exsign] I (M1) [Ex ia] I
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Systematic capability (SC) SC 3
Connection side control side
Maximum safe voltage_1 U 253 V AC (Attention! U is no rated voltage.)
UL approval E106378
Coding pin 1 and 2 trimmed For further information see system description.
Safety Integrity Level (SIL) SIL 3
Control drawing 16-534FM-12 (cFMus)
Signal type Digital Input
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/Output functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Certificate PF 09 CERT 1440 X
Control drawing_1 116-0364
Input Ex ia
Output/power supply functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mass approx. 105 g
Power dissipation ≤ 800 mW
Connection SL1: 6b
Switching point/switching hysteresis 2.1 ... 2.8 mA / approx. 0.3 mA
Electromagnetic compatibility EN IEC 61326-3-2:2018 , NE 21:2017 For further information see system description.
Maximum safe voltage U 253 V AC (Attention! U is no rated voltage.)
Marking_1 II 3G Ex nA IIC T4 Gc
IECEx marking [Ex ia Ga] IIC, [Ex ia] IIIC , [Ex ia] I
Open circuit voltage/short-circuit current approx. 8.4 V DC / approx. 11.9 mA
Response delay ≤ 1 ms
Power P 45 mW (linear characteristic)
Power consumption ≤ 1300 mW
EU-type examination certificate BASEEFA 07 ATEX 0302X
Display elements LEDs
Width 12.5 mm
Output type open collector transistor (internal fault bus)
P+F 倍加福 KCD2-SR-Ex1.LB.SP SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

商品名称: P+F 倍加福 KCD2-SR-Ex1.LB.SP SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

商品型号: KCD2-SR-Ex1.LB.SP

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 安全光栅

EU-type examination certificate BASEEFA 06 ATEX 0092 X
Control drawing 116-0477 (cULus)
Switching frequency ≤ 10 Hz
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Directive 2014/35/EU EN 61010-1:2010+A1:2019+A1:2019/AC:2019
Output I signal ; relay
Rated voltage U 19 ... 30 V DC
Rated current I ≤ 37 mA
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Display elements LEDs
Mass approx. 100 g
Voltage U 10.5 V
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
Labeling space for labeling at the front
Input Ex ia
Mechanical life 10 switching cycles
Current I 13 mA
Maximum safe voltage U 253 V AC (Attention! U is no rated voltage.)
UL approval E106378
Systematic capability (SC) SC 3
Pulse/Pause ratio min. 20 ms / min. 20 ms
Signal type Digital Input
Connection side control side
Maximum safe voltage_1 U 253 V AC (Attention! The rated voltage can be lower.)
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Output II signal or fault message ; relay
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Width 12.5 mm
Maximum safe voltage_2 U 40 V DC (Attention! U is no rated voltage.)
Rated values acc. to EN 60947-5-6 (NAMUR)
Marking II 3(1)G Ex ec nC [ia Ga] IIC T4 Gc , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] I
Power dissipation ≤ 750 mW
Power P 34 mW (linear characteristic)
Safety note If load voltage > 50 V, de-energize before removing the terminals.
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Configuration via DIP switches
Depth 114 mm
Ripple ≤ 10 %
Power consumption ≤ 750 mW
Safety Integrity Level (SIL) SIL 2
Degree of protection IP20
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Connection spring terminals
Electromagnetic compatibility NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
IECEx marking Ex ec nC [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
Control elements DIP switch
Height 119 mm
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Functional safety IEC/EN 61508:2010
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Contact loading Zone 2 : 50 V AC/2 A/cos φ > 0.75; 30 V DC/2 A resistive load
IECEx certificate IECEx BAS 06.0025 X
Minimum switch current 2 mA / 24 V DC
P+F 倍加福 KFD2-STC4-Ex2 SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

商品名称: P+F 倍加福 KFD2-STC4-Ex2 SIL-Capable Products for Hazardous Areas Safety Integrity Level 2

商品型号: KFD2-STC4-Ex2

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 隔离栅

Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , (W x H x D) housing type B2
EU-type examination certificate BAS 99 ATEX 7025 X
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
Power P 0.586 W
Rated voltage U 20 ... 35 V DC
Mass approx. 150 g
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Signal type Analog input
Electromagnetic compatibility NE 21:2011
UL approval E106378
Input signal 0/4 ... 20 mA
Frequency range field side into the control side: band width with 1 V signal 0 ... 7.5 kHz (-3 dB) safe area to hazardous area: band width with 1 V signal 0.3 ... 7.5 kHz (-3 dB)
Power dissipation 1.8 W
Certificate TÜV 99 ATEX 1499 X
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Height 124 mm
Output/power supply functional insulation, rated insulation voltage 50 V AC
Output signal 0/4 ... 20 mA (overload > 25 mA)
Rise time/fall time 20 µs
Safety Integrity Level (SIL) SIL 2
Labeling space for labeling at the front
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/Output functional insulation, rated insulation voltage 50 V AC
Current I 93 mA
Maximum safe voltage U 250 V (Attention! The rated voltage can be lower.)
Marking_1 II 3G Ex nA II T4
IECEx certificate IECEx BAS 04.0015X IECEx CML 15.0055X
Load 0 ... 550 Ω at 20 mA
Deviation at 20 °C (68 °F), 0/4 ... 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Settling time 200 µs
Influence of ambient temperature 0.25 µA/K
Ripple max. 50 µA
Protection against electrical shock UL 61010-1:2012
Control drawing 116-0428 (cULus)
Connection screw terminals
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex nA IIC T4 Gc
Available voltage ≥ 16 V at 20 mA, terminals 1+, 3
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Depth 115 mm
Degree of protection IP20
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Power consumption max. 2.7 W
Marking II (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] I
Voltage U 25.2 V
Connection side control side
Display elements LED
Width 20 mm
P+F 倍加福 KFD2-UFT-2.D 信号调节器 K-System (DIN rail, highly functional)

商品名称: P+F 倍加福 KFD2-UFT-2.D 信号调节器 K-System (DIN rail, highly functional)

商品型号: KFD2-UFT-2.D

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 隔离栅

Degree of protection IP20
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Open circuit voltage/short-circuit current_1 18 V / 5 mA
Collective error message Power Rail
Influence of ambient temperature_1 0.005 %/K (50 ppm)
Connection side control side
Display elements LEDs , display
Depth 115 mm
Programming interface programming socket
Output I, II signal, relay
Accuracy_1 < 30 µA
Interface/output III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Input III, IV/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Power consumption 2.5 W
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Measuring range 0.001 ... 1000 Hz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
UL approval E223772
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Contact loading_1 40 V DC
Output V analog
Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Connection screw terminals
Rated voltage U 20 ... 30 V DC
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Load max. 650 Ω
Current range 0 ... 20 mA or 4 ... 20 mA
Open loop voltage max. 24 V DC
Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Power dissipation 2.2 W
Influence of ambient temperature 0.003 %/K (30 ppm)
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Directive 2014/35/EU EN 61010-1:2010
Switching point/switching hysteresis logic 1: > 2.5 mA ; logic 0: < 1.9 mA
Input EN 60947-5-6:2000
Output III and IV signal , electronic output, passive
Output III, IV/input III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Output III, IV/power supply and collective error basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Signal type Digital Input
Labeling space for labeling at the front
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mass 300 g
Height 119 mm
Pulse duration min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Electromagnetic compatibility NE 21:2006
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Measuring time frequency measurement: < 100 ms
Configuration via operating buttons via PACTware
Mechanical life 5 x 10 switching cycles
Interface/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Input I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output V/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 V
Width 40 mm
Rated current I approx. 130 mA
Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)
Response delay ≤ 200 ms
Resolution_1 < 10 µA
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Output III, IV/V basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
P+F 倍加福 KFU8-UFT-2.D 信号调节器 K-System (DIN rail, highly functional)

商品名称: P+F 倍加福 KFU8-UFT-2.D 信号调节器 K-System (DIN rail, highly functional)

商品型号: KFU8-UFT-2.D

品牌名: P+F 倍加福

分类: 安全传感器

订货号:

类型: 隔离栅

Electromagnetic compatibility NE 21:2006
Programming interface programming socket
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output I, II signal, relay
Response delay ≤ 200 ms
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Switching point/switching hysteresis logic 1: > 2.5 mA ; logic 0: < 1.9 mA
Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Open circuit voltage/short-circuit current_1 18 V / 5 mA
Input EN 60947-5-6:2000
Input I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Display elements LEDs , display
Labeling space for labeling at the front
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Measuring range 0.001 ... 1000 Hz
Directive 2014/35/EU EN 61010-1:2010
Input III, IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output III, IV/input III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Output V/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Depth 115 mm
Configuration via operating buttons via PACTware
Pulse duration min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Output III, IV/V basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Interface/output III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Connection screw terminals
Power dissipation 2.2 W / 3.5 VA
Connection side control side
Mass 300 g
Height 119 mm
Width 40 mm
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)
Open loop voltage max. 24 V DC
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Power consumption 2.5 W / 4 VA
Load max. 650 Ω
Influence of ambient temperature 0.003 %/K (30 ppm)
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Degree of protection IP20
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Mechanical life 5 x 10 switching cycles
Contact loading_1 40 V DC
Output III and IV signal , electronic output, passive
Output III, IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Signal type Digital Input
Current range 0 ... 20 mA or 4 ... 20 mA
Influence of ambient temperature_1 0.005 %/K (50 ppm)
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Rated voltage U 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output V analog
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Measuring time frequency measurement: < 100 ms
Rated current I approx. 130 mA
Resolution_1 < 10 µA
Accuracy_1 < 30 µA